GDJF-2008 Partial Discharge Detector is measuring partial discharge for the products such as transformers, mutual inductors, HV switches, zinc monoxide arresters and power cables. It also can make type tests and monitor insulation operation.
This type has the advantages of high sensitivity, wide range of capacitance, being well equipped for input unit impedance detecting and more variants of frequency bands ( 9 in all). After proper setting, the discharge impulse amount can be read directly. The indicating and digital meters are shown simultaneously.
This detector is widely applied in power stations, manufacturers and institutions.
Testing sensitivity (shown in Table.1)
Input unit No. |
Tuning capacitance |
Unit |
Sensitivity(pC) (Unsymmetrical circuit) |
1 |
6-25-100 |
pF |
0.02 |
2 |
25-100-400 |
pF |
0.04 |
3 |
100-400-1500 |
pF |
0.06 |
4 |
400-1500-6000 |
pF |
0.1 |
5 |
1500-6000-25000 |
pF |
0.2 |
6 |
0.006-0.025-0.1 |
uF |
0.3 |
7 |
0.025-0.1-0.4 |
uF |
0.5 |
8 |
0.1-0.4-1.5 |
uF |
1 |
9 |
0.4-1.5-6.0 |
uF |
1.5 |
10 |
1.5-6.0-25 |
uF |
2.5 |
11 |
6.0-2.5-60 |
uF |
5 |
12 |
25-60-250 |
uF |
10 |
7R |
Resistance |
|
0.5 |
Table 1
Low terminal: 10KHZ, 20 KHZ, 40 KHZ (optional)
High terminal: 80 KHZ, 200 KHZ, 300 KHZ (optional)
Coarse control – there are 6 steps for coarse tuning, the gain of each step is 20±1db
Fine control ≥ 20 db
Width of window, adjustable 15o-150o
Window position, adjustable 0o-170o
Two windows can be opened simultaneously or separately.
Digital display
PD display: LED 3½ digits
0-100.0 Error <±5% (full scale)
Frequency: 50Hz,100Hz,150Hz, 200Hz,400Hz
Elliptic display color is yellow
Elliptic rotation: each step is 30°, 120 ° rotation can be made.
Display: ellipse – straight line
Enable to adjust high-frequency time base ellipse to normal size according to input voltage (13-275V)., intake power < 1 VA.
Lock required waveform of any time to facilitate observation and analysis
Range: 100KV (Can be expanded)
Display by 3½ digital voltage meter
Accuracy: better than ±5% (full scale)