GDSL-BX-200 Primary Current Injection Test Set

I. General Information

GDSL-BX-200 Primary Current Injection Test Set, is mainly used for testing current transformer, motor protector, air switch, switch cabinet, circuit breaker, protection screen and etc.

II. Features

  • PVC panel, simple and neat.
  • With low power, big capacity autotransformer regulator and converter inside.
  • Quick connects, lock design, good current-through capability.
  • Built-in quick plug with high safety, to ensure reliable cable connection and improve test efficiency.
  • Current range can be changed, easy to read.
  • Engineering plastics box, dust-proof and waterproof, IP67 class.
  • Portable design, suitable for on-site testing.
  • Damping design, to ensure reliable transportation
  • Zero start function to prevent the test objects from damage caused by high current impulse. The equipment only can be started from zero.
  • Impulse selection function. The required current can be output directly without zero protection function when making quick-break testing for circuit breaker.
  • Accurate measurement. LCD digital indicator to display output current and voltage. The resolution of output current is 1A .
  • Output 0-50A AC current, suitable for over current quick break testing of secondary protection.
  • Action time can be tested synchronously.
  • More calibrations can be series connected at the same time to improve working efficiency .
  • Directly display primary current and secondary current, convenient for CT/PT turn ratios calibration test. (Optional)

III. Specifications

  • Power supply: AC 220V 50Hz.
  • Output power: 3kVA.
  • Output current: 500A in series,1000A in parallel.
  • Output voltage: 6V in series, 3V in parallel.
  • Current can be adjusted smoothly and continuously. The accuracy is 1.0%.
  • Output current is standard sine wave, waveform distortion is less than 5%.
  • Secondary injection current: 50A
  • Output current: RMS continuous adjustable.
  • The action time of test object can be tested, the lock action time is also can be recorded at the same time.
  • Test range: 0.001S-999.999S, resolution 1ms, error: 0.005%, range: ±2digits
  • Duty Cycle: 5mins ON, 10mins OFF.