GDTF-GSW AC Resonant Test System (for Generators)

General Information

GDTF series AC Resonant Test System for Generators can be used by adjusting inductance of the reactor, or adjusting the work way of resonant frequency of the system to achieve resonance.You can also use both two methods to achieve resonance.In the voltage boosting process, if the resonant point deviate,you can find it exactly by the way of fine tuning frequency,which ensure a high Q value and reduce power capacity and volume weight of test equipment.

Features

  • Smaller size,lighter weight compared with same voltage level,same capacity generator AC withstand voltage test equipments.Single equipment is no more than 60kg,easy to move.
  • Advanced principle of whole set device and new frequency&inductance modulation technology, strictly ensure generator power frequency withstand voltage test requirements. Wide application scope.
  • Equipped with 20Hz-300Hz variable control source. Good protection and output waveform,high stability.With multiple working mode,easy to operate.
  • Power supply of 220V or 380V, convenient for on-site power sourcing;
  • Max.Q point can be found exactly by the mode of first inductance modulation and later frequency modulation,to avoid resonance deviation because of voltage boosting;
  • Flexible configuration and strong extension. Meet all capacitive test object testing requirements in power system.
  • Power frequency test mode or Variable frequency test mode.
  • Multi-use, cost-effective.

Technical specifications

  • Rated output voltage: 0 ~ 50kV (RMS) or below.
  • Output frequency: 45 - 300Hz.
  • Waveform: pure sine wave, THD ≤ 1%.
  • Max. capacity: 2000kVA or below.
  • Duty cycle: continuous working 15mins one time at full power output.
  • Quality factor: 10 - 40.
  • Frequency adjustment sensitivity: 0.1HZ, instability of <0.05%.
  • Power supply: 220V or 380V ± 15%, 50HZ ± 5%.

Common Configuration of Power Frequency test mode

GDTF (L) - 540/60

Input voltage (V)

380

Output voltage (kV)

0-60

Capacity (kVA)

540

Application scope

Generator--capacitance to the ground 0.1-0.7 μF

Main configurations

60kV/3A Fixed reactor 2 se ts

60kV/3A Adjustable reactor 1 set

Capacitive divider 60 kV

GDTF (L) - 1080/60

Input voltage (V)

380

Output voltage (kV)

0-60

Capacity (kVA)

1080

Application scope

Generator--capacitance to the ground 0.3-1.5 μF

Main configurations

60kV/4.5A Fixed reactor 2 sets

60kV/4.5A Adjustable reactor 2 sets

Capacitive divider 60kV

GDTF (L) - 2160/60

Input voltage (V)

380

Output voltage (kV)

0-60

Capacity (kVA)

2160

Application scope

Generator--capacitance to the ground 0.5-2.5 μF

Main configurations

60kV/9A Fixed reactor 2 sets

60kV/9A Adjustable reactor 2 sets

Capacitive divider 60kV

Common configuration of Variable Frequency test mode

GDTF- 100 / 50

Input voltage (V)

380

Output voltage (kV)

0- 50

Capacity (kVA)

100

Application scope

Generator--capacitance to the ground 0.07-0.13 μF

10 kV (300 mm² ) cable ≤ 1 km

Main configurations

50kV/1A Fixed reactor 1 set

50kV/1A Adjustable reactor 1 set

Capacitive divider 50kV

GDTF-150/50

Input voltage (V)

380

Output voltage (kV)

0- 50

Capacity (kVA)

150

Application scope

Generator--capacitance to the ground 0.13-0.2 μF

10 kV (300 mm² ) cable ≤ 1.5 km

Main configurations

50kV/1.5A Fixed reactor 1 set

50kV/1.5A Adjustable reactor 1 set

Capacitive divider 50 kV

GDTF- 225/50

Input voltage (V)

380

Output voltage (kV)

0- 50

Capacity (kVA)

225

Application scope

Generator--capacitance to the ground 0.2-0.27 μF

10 kV (300 mm ² ) cable ≤ 2.5 km

Main configurations

50kV/1.5A Fixed reactor 2 sets

50kV/1.5A Adjustable reactor 1 set

Capacitive divider 50 kV

GDTF- 360/60

Input voltage (V)

380

Output voltage (kV)

0- 60

Capacity (kVA)

360

Application scope

Generator--capacitance to the ground 0.27-0.33 μF

Main configurations

60kV/2A Fixed reactor 1 set

60kV/2A Adjustable reactor 1 set

Capacitive divider 60kV

 

 

You may need other related products of the GDTF-GSW AC Resonant Test System (for Generators)