    GD6100C Transformer Oil Tan Delta Tester hits:

    Product Description

     GD6100C is high-precision instrument for testing dielectric loss factor and DC resistivity of insulating oil or other insulating liquids. With its integrated structure, it contains major components such as dielectric loss oil cup, temperature controller, temperature sensor, dielectric loss test bridge, AC testing power supply, standard capacitors, Megger, DC high voltage source.

    Features

    • Big LCD screen, with backlight.
    • Friendly interface. Automatic storage and print test result.
    • Oil cup is three electrode, gap with 2mm. The oil sample can be evacuated without dismantling oil cup. Oil cup can be cleaned by oil sample.
    • With MF induction heating and PID temperature control. The temperature will be controlled within preset temperature error range strictly.
    • With SF6 gas 3-pole capacitor. Its tan delta and capacitance will not be affected by environmental temperature and humidity.
    • AC power supply is AC-DC-AC mode, to avoid fluctuation of mains voltage and frequency.
    • With over-voltage, over-current, short circuit protection. 
    • When the temperature is over 120degree, heating stops.
    • Parameters are set easily. Temperature range 0-125℃, AC voltage range 500-2200V, DC voltage range 0-500V.
    • With clock. Test date and time can be saved and printed together with test result.
    • Calibration function of cleaned dry cell. Capacitance and dielectric loss factor measurement of dry cell can determine thecleaning and assemble conditions. Calibration data is saved automatically which is more convenient to accurately calculate relative permittivity and DC resistivity.

    Specifications

    • Power supply: AC 220V±10%
    • Power frequency: 50Hz/60Hz ±1%
    • Measuring range:

    Capacitance: 5pF-200pF

    Relative Permittivity: 1.000-30.000

    Dielectric loss factor: 0.00001-100

    DC Resistivity: 2.5MΩm-20TΩm

    • Measuring accuracy:

        Capacitance: ± (1% of reading+0.5pF)

        Relative Permittivity:±1% of reading

        Dielectric loss factor:± (1% of reading+0.0001)

        DC Resistivity:±10% of reading

    • Resolution:

        Capacitance:0.01pF

        Relative capacitivity: 0.001

        Dielectric dissipation factor: 0.00001

    • Temperature range: 0-125℃
    • Temperature measurement error: ±0.5℃
    • AC Test Voltage (RMS): 500~2200V Continuous adjustment, frequency 50Hz
    • DC Test Voltage: 0-500V  Continuous adjustment
    • Power consumption: 100W
    • Dimension: 500×360×420mm
    • Weight: about 22Kg
    CONTACT US
    Address: F/10, Block B7, JinYinTan Modern Enterprise City, Dongxihu District, Wuhan, China
    Email: info@hvhipot.com
    Skype: hvhipot@hotmail.com
    Tel: +86-27-85568138
    Fax: +86-27-65606183
    NAVIGATION
  • Company

    Company

  • Product

  • News

  • Services

  • Contact us

  • All Rights Reserved Copyright@HV Hipot Electric Co.,Ltd.