• 0
    • 0
    GDKC-12A Circuit Breaker Analyzer hits:

    Product Description

    High voltage circuit breaker is one of the most important control equipment in the power system. 

    GDKC-12A is used to test the dynamic characteristics of high voltage circuit breaker. It is easy to operate, with high accuracy. 


    Features

    • Time: the open/close time, in phase synchronizationphase-to-phase synchronization of 12contacts.
    • Reclose: close-open, open-close, open-close-open time for each contact.
    • BounceClose bounce time, times, process and waveform of each contacts.
    • VelocityVelocity at contact touch, maximum speed, time-range characteristic curve. 
    • TravelTotal travel, open travel, over traveltravel overshoot, bounce amplitude.
    • Current: open/close current, current waveform diagram of the open/close coil.
    • Operation voltage: built-in DC30~250V/20A digital, adjustable power source of breaker, automatically complete LV action test of circuit breaker and measure action voltage value of circuit breaker. 
    • It is suitable to test the mechanism parameters of all types of SF6 circuit breaker, GIS combination electric equipmentvacuum circuit breaker, oil circuit breaker.
    • Strong anti-interfere ability. It also can easily test and accurately measure even interbus is live in 500kV substation.
    • With universal velocity sensor(optional), linear velocity sensor, rotary sensor, easy to install.
    • Only one time action to obtain all data and corresponding waveform of breaker mechanism test.
    • Storage test data, built-in real-time clock, which is convenient to save test date and time.
    • LCD screen display, with contrast adjustment and power-off memory.
    • Built-in printer, to get all data and diagram at any time quickly.

    Specifications

    • 1.1 Using Environments
      Input Power: 220V± 10% 50Hz± 10% Air Pressure: 86~106kpa
      Temperature: -10~40 degree
      Humidity: 80%RH

      1.2 Safety Performance
      Insulation Resistance>2MΩ
      Dielectric Strength: Chassis can withstand voltage 1.5kv and power frequency for 1 minute without flash-over and arcing.

      1.3 The Basic Parameters

      A. Time: Range 25000.0ms resolution 0.01ms
      Error 250ms 0.01ms ± 1digit
               2500ms 0.1ms ± 1digit
               25000ms 1ms ± 1digit
      Same period
      B. Velocity: Range 20.00m / s resolution 0.01m / s
      Error 0-2m / s ± 0.1m / s ± 1digit
      Above 2ms ± 0.2m / s ± 1 digit

      C.Range: 

       

      Range

      Resolution

      Error

      Vacuum breaker

      50.0mm

      0.1mm

       

      0.1±1digit

      SF6 circuit breaker

      300.0mm

      1mm

      Oil circuit breaker

      600.0mm


      D. Current: Range 20.00A resolution 0.01A
      E. Output power: DC0 ~ 300V digital adjustable / 20A (instantaneous work), resolution 1V.
      F. Dimensions: 360mm (L) × 280mm (W) × 300mm (H)
      G. Weight: 10kg


    CONTACT US
    Address: F/10, Block B7, JinYinTan Modern Enterprise City, Dongxihu District, Wuhan, China
    Email: info@hvhipot.com
    Skype: hvhipot@hotmail.com
    Tel: +86-27-85568138
    Fax: +86-27-65606183