    GDTF-240/240 Variable Frequency AC Resonant Test System hits:

    Product Description

    GDTF-240/240 is applied for hipot test to 145KV GIS with 6 big intervals and 6 small intervals( the big interval is 1000pF, the small interval is 500pF), the capacity is less than 0.009uF, the testing frequency is 30-300Hz, the testing voltage is 220KV and the testing time is 1min.

     

    Advantages in the power system application :

    1. Rapidly reduce the required power supply capacity. The power source of series resonance uses the resonant reactor and test object capacitance to generate high voltage and high current. In the whole system, the power supply only need to supply the part of active loss. Therefore, required test power is the 1 / Q of test capacity.

    2. Weight and volume of the device are greatly reduced.

    3. The output voltage waveform is improved. Resonanpower source is resonant filter circuit, which improve the distortion of output voltage waveform and obtain good sine wave. It greatly prevent the test object free from breakdown of harmonic peak.

    4. To avoid large short-circuit current burn the fault point. In the series resonant state, when the test objectinsulation weakness is breakdown, circuit detune immediately, and the loop current rapidly drop to 1 / Q of normal testing currentWhile tested by parallel resonant or test transformer, the breakdown current rise dozens of times immediately. So series resonant can find the insulation weakness effectively but not exist large short-circuit current breakdown the fault point.

    5Any recovery overvoltage is not appearedWhen the test object breakdown, due to resonance loss the resonant conditions, high voltage also disappear immediately, arc extinguish at once, and the time ofrecover voltage is very long, it will disconnect power supply before reaching the flashover voltage. The voltage recovery process is a kind of energy accumulation of intermittent oscillation, the process is long and any recoverovervoltage will not appeared.



    Features

    1. With the function of over-voltage, over-current, zero-start, system detune (flashover) protection. Over-voltage, over-current protection value can be set accordingly to user’ need. Flashover protection action when flashover and record the flashover voltage value for testing analyze.

    2.The unit piece of the device is light. Suitable for field use.

    3.There are three kinds of working mode for user choosing according to on-site condition.

    Automatic mode Manual mode,  Automatic tuning manual boost mode.

    4. Data can be stored, and the series numbers are figures which is easy for identification and searching.

    5. Frequency starting point can be setting in the specified scope when the device sweep frequency automatically, sweep frequency direction can choose upward or downwardmeanwhile LCD displays thescanning curve, which is convenient for user to know if the resonant point find or not intuitively.

    6. Adopted with DSP technology, which can increase or decrease functions and updated accordingly to the user’s need, it also makes the human-machine interface more humanized.




    Specifications

    GDTF - means manufacturers code.

    240kVA means the maximum rated capacity of the equipment, the unit is kVA

    240kV means the output voltage of the equipment, the unit is kV.

    1. The rated voltage:
    240kVmeet 145KV GIS with 6 big intervals and 6 small intervals AC hipot test.
    Working frequency: 30~300Hz, testing voltage220kV, testing time 1min
    2. Output voltage waveform distortion rate: < 1.0%
    3. Allowing continuous working time: rated condition one time 60s.
    4. Quality factor of the equipment: Q >50
    5. Quality factor of GIS in full load test: Q > 20 ( Related to load)
    6. Input power supply: Single phase 220V or three phase 380V;
    7. Frequency adjusting range: 30-300Hz
    8. System measuring precision: 1.5%

    9. Over-voltage, over-current, zero-start protection


    Parameters for Individual Parts

    1. Variable frequency power supply  GDTF -15kW/220/380V  (1 set)

    • Rated output capacity: 15kW
    • Working power supply: 220/380±10%V(single/3-phase), power frequency
    • Output voltage: 0-400V, single phase
    • Rated input current: 37.5A
    • Rated output current: 37.5A
    • Voltage resolution: 0.01kV
    • Voltage measuring accuracy: 1.5%
    • Frequency adjusting range: 30-300Hz
    • Frequency adjusting resolution: ≤0.1Hz
    • Frequency stability: 0.1%
    • Working time: constant working of 5mins under rated capacity.
    • Temperature rise:  65K after constant working of 5mins under rated capacity.
    • Noise: ≤50dB
    • Weight: approx. 18kg.

    2. HV Reactor  GDDK-40kVA/40k (6 sets)

    • Rated capacity: 40kVA
    • Rated voltage: 40kV
    • Rated current: 1A
    • Inductance: 100H (per set)
    • Quality factor: 30 (f=45Hz)
    • Type: Dry type
    • Weight: approx. 45kg

    3. Exciting Transformer  GDJL-15kVA/15kV/0.4kV (1 set)

    • Rated capacity: 15kVA
    • Input voltage: 0-400V, single phase
    • Output voltage: 15kV
    • Type: Dry type transformer
    • Weight: approx. 58kg

    4. Capacitive Divider  GDFR-120kV/1000pF   (2 sets)

    • Rated voltage: 120kV
    • Capacitance: 1000pF
    • Dielectric loss: tgσ ≤0.5%
    • Divider ratio: 3000:1
    • Measuring accuracy: 1.5%
    • Weight: approx. 26kg 



    CONTACT US
    Address: F/10, Block B7, JinYinTan Modern Enterprise City, Dongxihu District, Wuhan, China
    Email: info@hvhipot.com
    Skype: hvhipot@hotmail.com
    Tel: +86-27-85568138
    Fax: +86-27-65606183
    NAVIGATION
  • Company

    Company

  • Product

  • News

  • Services

  • Contact us

  • русский

  • All Rights Reserved Copyright@HV Hipot Electric Co.,Ltd.