China High Quality Capacitor In Transformer Suppliers – AC High Voltage Test Sets for GIS – HV Hipot
China High Quality Capacitor In Transformer Suppliers – AC High Voltage Test Sets for GIS – HV Hipot Detail:
Applications
● Transformer
● GIS system
● SF6 switchgear
● Cables
● Bushing
● Insulator
● CT/PT
● Other capacitive devices
Features
● Small temperature rises at rated load. Dry or Oil type reactors, high mechanical strength, good insulation, nice and reliable.
● Adjustable capacity of frequency control source. Strong protection, good stability. With multiple working mode, easy to operate.
● With 220V or 380V single phase power, convenient for on-site power sourcing.
● Flexible configuration. Different type reactors for optional, meet different test object requirements. Multifunctional, cost effective.
Specifications
● Rated output voltage: based on different test objects.
● Output frequency: 20- 300Hz.
● Waveform: pure sine wave, THD <1.0%.
● Max. capacity: 1000kVA and below.
● Duty Cycle: Continuous working time 15mins one time at full power output. (or customer demand.)
● Frequency adjustment sensitivity: 0.1Hz, instability <0.05%.
● Power Supply: 380/220V ± 15%/50Hz ± 5%.
Product Configuration
GDTF-108/108 |
|
Input voltage (V) |
380 |
Output voltage (kV) |
0-108 |
Capacity (kVA) |
108 |
Application scope |
31500kVA or below |
35kV power transformer |
|
35kV circuit breaker and bus bar, insulators |
|
10kV (300 mm²) cable 2000m |
|
35k V (300 mm²)cable 500m |
|
Main configurations |
5kW Variable frequency source 1 set |
5kVA Exciting transformer 1 set |
|
Reactors 27kV/1A 4sets |
|
Capacitive divider 100kV |
|
GDTF-216/216 |
|
Input voltage (V) |
380 |
Output voltage (kV) |
0-216 |
Capacity (kVA) |
216 |
Application scope |
110kV Circuit breaker and bus bar |
110kV GIS |
|
35kV(300 mm²) cable 1500m |
|
10kV(300 mm²) cable 3km |
|
110kV full insulation Transformer |
|
Main configurations |
10kW Variable frequency source 1 set |
10kVA Exciting transformer 1 set |
|
Reactors 54kV/1A 4sets |
|
Capacitive divider 200kV |
|
GDTF-270/270 |
|
Input voltage (V) |
380 |
Output voltage (kV) |
0-270 |
Capacity (kVA) |
270 |
Application scope |
110kV GIS and transformer |
110kV GIS and transformer |
|
35kV (300 mm²) cable 2km |
|
Main configurations |
15kW Variable frequency source 1 set |
15kVA Exciting transformer 1 set |
|
Reactors 54kV/1A 5sets |
|
Capacitive divider 300kV |
|
GDTF-400/400 |
|
Input voltage (V) |
380 |
Output voltage (kV) |
0-400 |
Capacity (kVA) |
400 |
Application scope |
220kV GIS and transformer |
10kV (300 mm²) cable 4km |
|
35kV (300 mm²) cable 1km |
|
Main configurations |
20kW Variable frequency source 1 set |
20kVA Exciting transformer 1 set |
|
Reactor |
|
Capacitive divider 400kV |
|
GDTF-520/260 |
|
Input voltage (V) |
380 |
Output voltage (kV) |
0-260 |
Capacity (kVA) |
520 |
Application scope |
110KV Circuit breaker and bus bar |
110kV GIS |
|
110kV (300 mm²) cable 800m |
|
35kv (300 mm²) cable 3km |
|
10kV (300 mm²) cable 6km |
|
110kv full insulation Transformer |
|
Main configurations |
25kW Variable frequency source 1 set |
25kVA Exciting transformer 1 set |
|
Reactor 65kV/2A 4sets |
|
Capacitive divider 300kV |
|
GDTF-500/500 |
|
Input voltage (V) |
380 |
Output voltage (kV) |
0-500 |
Capacity (kVA) |
500 |
Application scope |
220kV or below CT/PT |
220kV or below bushing |
|
220kV or below Insulators, disconnectors |
|
220kV or below Circuit breaker |
|
220kV or below Insulation Instrument |
|
Main configurations |
20kW Variable frequency source 1 set |
20kVA Exciting transformer 1 set |
|
Reactor 125kV/1A 4sets |
|
Capacitive divider 500kV |
|
GDTF-600/600 |
|
Input voltage (V) |
380 |
Output voltage (kV) |
0-600 |
Capacity (kVA) |
600 |
Application scope |
110kV (300 mm²) cable 800m |
35kv (300 mm²) cable 110m |
|
35-220kV GIS, transformers, insulators |
|
Main configurations |
30kW Variable frequency source 1 set |
30kVA Exciting transformer 1 set |
|
Reactor 120kV/1A 5sets |
|
Capacitive divider 600kV |
|
GDTF-800/800 |
|
Input voltage (V) |
380 |
Output voltage (kV) |
0-800 |
Capacity (kVA) |
800 |
Application scope |
110kV (300 mm²) cable 800m |
220kv (300 mm²) cable 500m |
|
35-500kV GIS, transformers, insulators |
|
Main configurations |
40kW Variable frequency source 1 set |
40kVA Exciting transformer 1 set |
|
Reactor 200kV/1A 4sets |
|
Capacitive divider 800kV |
Product detail pictures:
Related Product Guide:
We have quite a few great team customers very good at internet marketing, QC, and dealing with kinds of troublesome trouble while in the output approach for China High Quality Capacitor In Transformer Suppliers – AC High Voltage Test Sets for GIS – HV Hipot , The product will supply to all over the world, such as: Albania, Hamburg, Angola, The products has a good reputation with competitive price, unique creation, leading the industry trends. The company insists on the principle of win-win idea, has establishedglobal sales network and after-sales service network.
By Tom from Canada - 2018.05.13 17:00
The company account manager has a wealth of industry knowledge and experience, he could provide appropriate program according our needs and speak English fluently.
By Barbara from Maldives - 2017.06.22 12:49