China High Quality devices used for relay testing Factories – GDJB-II SECONDARY CURRENT INJECTION TEST SET – HV Hipot
China High Quality devices used for relay testing Factories – GDJB-II SECONDARY CURRENT INJECTION TEST SET – HV Hipot Detail:
Features
A. Working conditions
1. Power supply: AC 220V±10%,50Hz
2. Working environment: Temperature -10℃~40℃; Humidity: ≤85%
3. Atmosphere: 86-106kPa
B. Output power supply
1. AC voltage: 0-220V/3A Adjustable
2. AC current: 0-100A/7V (200A can be customized); 0-20A/25V Adjustable; 0-5A/5V Adjustable
3. DC voltage: 0-220V/3A Adjustable
4. DC current:0-20A/25V
5. Fixed voltage output: DC 24V/48V/110V/220V
6. Current/Voltage accuracy: ±1%.
C. Performance Index
1. Ammeter and voltmeter: 41/2 digit.
2. Digital millisecond meter: 0-99.9999s(999.999s can be customized) Resolution: 0.1ms.
D. Functions
1. Measure relay: Measure start value, return value and drop-off to pick-up ratio of current, voltage relay.
2. Time relay: Measure start value, return value and action time.
3. Intermediate relay: Measure all kinds of coil with start. Remain start value, return value, holding value and action time of coil intermediate relay.
4. Reclosing relay: Charge test of capacitance, charge time, reclosing time and middle components test.
5. Differential relay: DC Excitation test, Braking test, Volt-ampere characteristic test.
6. Other common relays and LV circuit breaker.
Accessories
Name | Qty |
GDJB-II secondary injection test set | 1 pc |
Power cable | 1 pc |
Test line | 6 pcs |
Current line | 2 pcs |
Fuse | 4 pcs |
Manual | 1 copy |
Certificate | 1 copy |
Product detail pictures:







Related Product Guide:
We're convinced that with joint endeavours, the business between us will bring us mutual benefits. We are able to guarantee you products high quality and competitive value for China High Quality devices used for relay testing Factories – GDJB-II SECONDARY CURRENT INJECTION TEST SET – HV Hipot , The product will supply to all over the world, such as: Greece, Argentina, Saudi Arabia, We also have the strong ability of integration to supply our best service, and plan to build the warehouse in the different countries around the world, that will be more conveniently to service our customers.

This is the first business after our company establish, products and services are very satisfying, we have a good start, we hope to cooperate continuous in the future!
