Attaining consumer satisfaction is our firm's purpose for good. We'll make wonderful efforts to produce new and top-quality merchandise, meet up with your special necessities and supply you with pre-sale, on-sale and after-sale products and services for Safely Discharge Capacitor, Testing Capacitors In Circuit, Filter Capacitors, With the eternal goal of "continuous quality improvement, customer satisfaction", we are sure that our product quality is stable and reliable and our products are best-selling at home and abroad.
China High Quality digital meter price Factories – Dielectric Loss Tester for Live Capacitive Equipment GDDJ-HVC – HV Hipot Detail:

General Information

There are usually two ways to monitor the insulation condition of high voltage electrical equipment in substations: online monitoring and live (portable) online detection. The former one can obtain the characteristic parameters reflecting the abnormal insulation of the equipment at any time, which is convenient for automatic management. However, the investment is relatively large, the installation and construction are relatively troublesome, and regular maintenance is needed. For the latter, it has the advantages of low investment, highly targeted, easy to install, maintain and update. If the sampling unit is installed in the electrical equipment in advance, a regular detection can be done for electrical equipment in operation, and insulation flaw can be found in time, so as to prolong the pretest period of power failure and completely replace on-line monitoring method.

GDDJ-HVC dielectric loss tester for live capacitive equipment can be used to measure dielectric loss and capacitance of capacitive equipment (bushing, CT, CVT, coupling capacitor), and detect insulation flaws effectively.

Features

1. External hole type current sensor with high precision is often used instead of the traditional sampling unit, which includes more than one switch circuit. During testing, multiple short tabs are needed to lead end shielding current to test instrument. GDDJ – HVC uses traditional straight-through structure, can be installed near the equipment, lead of end shielding is not broken, and the length is very short, which avoid open circuit of end shielding. The sensor can accurately detect signals within 100μA~700mA. Impedance of sensor is low, can withstand power frequency current 10A and lightning impulse current 10kA, meet use conditions of online detection.

2. The sampling unit adopts die-casting aluminum shell sealing waterproof design, and adopts waterproof cable connector for secondary output, which is convenient for connection; After the sensor is installed, it is normally not energized. For testing, only the secondary cable of the sampling unit need be connected, and “plug and play” can be achieved without any operation on the end shielding signal cable.

3. The core processor of the instrument is American TI 32-bit floating-point high performance digital signal processor (DSP), which runs a real-time operating system and adopts an extended 16-bit, high-speed, multi-channel synchronous sampling analog digital converter (A/D) to realize real-time measurement and high-precision calculation of the monitored quantity. Able to monitor multiple devices simultaneously.

4. Two on-line detection methods for dielectric loss can be provided, which can measure dielectric loss difference and capacitance ratio of two capacitive devices in the same phase, and PT secondary voltage can be used as the reference signal to measure the capacitance and dielectric loss of the device. Using the compensating current sensor and advanced digital filtering technology, the problem of dielectric loss precision and stability is solved, combined with perfect electromagnetic shielding measures and advanced processing technology, digital filtering can ensure dielectric loss test results are not affected by the influence of harmonic interference and pulse interference, with absolute precision up to ±0.05%.

5. With the detection of dielectric loss difference and capacitance ratio of in-phase capacitive equipment, it can not only avoid the distortion of dielectric loss test result caused by using PT secondary voltage as the reference signal, but also help to reduce the influence of phase-to-phase electric field interference.

6. The detector is equipped with a large LCD screen for displaying the monitored voltage, current, dielectric loss, resistive current, capacitive current and other data.
 
7. The tester not only has the function of live detection, but also can monitor the equipment online for a long time, and automatically record the monitored data.

8. The system adopts external sensors instead of “traditional sampling unit”, which can be easily upgraded from “live detection” to “online monitoring” under normal operation of the equipment. There is no need to remove the installed sensors, no need to disable the device, just add a monitoring unit (IED).

9. The detector adopts portable design, simple to operate, the lithium battery in the machine can maintain 8 hours of continuous working time, fully meet the requirements of field use.

Specification

Main unit

Power supply

Maintenance-free battery

Cable

30m, 2 pieces

Ambient temperature

-45~60℃

Display

Large screen LCD display, suitable for outdoor use.

Size

430*340*160mm

Weight

5kg

Measurement range & accuracy

Current

Cx=100μA~1000mA, Cn=100μA~1000mA

Accuracy: ±(0.5%+1digit)

Voltage

Vn=3V~300V

Accuracy: ± (0.5%+1 digit)

Dielectric loss

Tanδ= -200%~200%

Accuracy: ±0.05%

Capacitance ratio

Cx:Cn=1:1000~1000:1

Accuracy: ± (0.5%C+1 digit)

 

Capacitance

Cx=10pF~0.3μF

Accuracy: ±(0.5%C+2pF)

Note: actual measurement accuracy is related with current of test object and accuracy of PT (or CVT) in use.

Resistive current

Irp=10μA~200mA (peak)

Accuracy: ±(0.5%+1digit)

Capacitive current

Icp=10μA~200mA

Accuracy: ±(0.5%+1digit)

Other characteristics

Harmonic suppression

Waveform distortion of input current signal will not affect the measurement accuracy.

 Power management

 

When the battery power in the machine is low or has not been measured for a long time, it will give sound alarm and automatically shut down.

Charging time

12~24 hours in shutdown state, intelligent charging system, power-off protection after fully charges.


Product detail pictures:

China High Quality digital meter price Factories –  Dielectric Loss Tester for Live Capacitive Equipment GDDJ-HVC  – HV Hipot detail pictures

China High Quality digital meter price Factories –  Dielectric Loss Tester for Live Capacitive Equipment GDDJ-HVC  – HV Hipot detail pictures


Related Product Guide:

Our goal is to provide high quality products at competitive prices, and top-notch service to customers around the world. We are ISO9001, CE, and GS certified and strictly adhere to their quality specifications for China High Quality digital meter price Factories – Dielectric Loss Tester for Live Capacitive Equipment GDDJ-HVC – HV Hipot , The product will supply to all over the world, such as: Milan, United States, Armenia, Our R&D department always designs with new fashion ideas so we could introduce up-to-date fashion styles every month. Our strict production management systems always ensure stable and high quality products. Our trade team provides timely and efficient services. If there are any interest and inquiry about our products, please contact us in time. We would like to establish a business relationship with your honored company.
  • Although we are a small company, we are also respected. Reliable quality, sincere service and good credit, we are honored to be able to work with you!
    5 Stars By Freda from Namibia - 2017.11.20 15:58
    This company has the idea of "better quality, lower processing costs, prices are more reasonable", so they have competitive product quality and price, that's the main reason we chose to cooperate.
    5 Stars By Abigail from Brisbane - 2018.10.01 14:14

    Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us