China High Quality Gas Leak Detector Usa Manufacturer – GDSF-311WP SF6 Dew Point and Purity Tester – HV Hipot
China High Quality Gas Leak Detector Usa Manufacturer – GDSF-311WP SF6 Dew Point and Purity Tester – HV Hipot Detail:
General Information
GDSF-311WP is ideal instrument when it is necessary to test water content and purity of SF6 gas. The core component is DRYCAP series sensors produced by Finland Vaisala company. With professional hardware chips and excellent software algorithms of STMicroelectronics, we have produced a new generation of gas moisture test instrument.
Application
● Moisture monitoring of SF6 gas electrical equipment for electric power
● SF6 gas cylinder gas quality test
● High purity gas manufacturing
● Semiconductor industry dry gas supply
● Research and development use
● Clean room/dry house monitoring
● Metal heat treatment site and laboratory industrial gas humidity detection, such as air, CO2, N2, H2, O2, SF6, He, Ar and other inert gases.
Features
Specification
SF6 Humidity
● Measurement method: Resistive and Capacitive measurement principle
● Measurement range: dew point -80℃–+20℃(support ppmv)
● Accuracy: ±1℃
(when the dew point temperature is below 0 ℃, the sensor output is the frost point)
● Response time: 63% [90%]
+20→-20℃ Td 5s[45s]
-20→-60℃ Td 10s[240s]
● Resolution: 0.01℃
● Repeatability: ± 0.5 ℃
● Display unit: ℃, ppm, ℃P20(converted value at 20℃)
● Gas flow: 400-600ml/min
● Flow display: 0-1000mL digital flow meter
● Sample gas pressure: ≤1MPa
SF6 Purity
● Measurement method: TCD technology.
● Measuring range: 0 ~ 100% SF6.
● Accuracy and repeatability: ± 0.5%, nothing to do with the flow.
● Power supply: 220VAC±10%, 50Hz, AC/DC use, over-charge protection, continuous working is no lower than 8hours.
● Use environment temperature: -20–+60℃
● Environment humidity: 90%RH
● Measurement value influence: No effect of pressure and flow
● Dimension: 395*295*155mm
● Weight: about 2kg.
Accessories
Main Tester | 1 piece |
Teflon pipe(include flow adjustment valve and fast connector) | 1 set |
Tail pipe | 1 set |
Spare parts | 1 set |
Charger | 1 piece |
User’s Guide | 1 piece |
Test Report | 1 piece |
Product detail pictures:

Related Product Guide:
As for competitive charges, we believe that you will be searching far and wide for anything that can beat us. We will state with absolute certainty that for such excellent at such charges we have been the lowest around for China High Quality Gas Leak Detector Usa Manufacturer – GDSF-311WP SF6 Dew Point and Purity Tester – HV Hipot , The product will supply to all over the world, such as: Serbia, Greece, South Korea, Our mission is "Provide Goods with Reliable Quality and Reasonable Prices". We welcome customers from every corner of the world to contact us for future business relationships and achieving mutual success!

It is not easy to find such a professional and responsible provider in today's time. Hope that we can maintain long-term cooperation.
