China High Quality megger resistance tester Factories – GDCR1000C Non-contact Phase Sequence Tester – HV Hipot

China High Quality megger resistance tester Factories – GDCR1000C Non-contact Phase Sequence Tester – HV Hipot

Brief Description:


Product Detail

Product Tags

Related Video

Feedback (2)

We're convinced that with joint endeavours, the business between us will bring us mutual benefits. We are able to guarantee you products high quality and competitive value for Surge Generator, Capacitance And Capacitor, Online Pd Test, We are sincerely looking forward to cooperate with buyers all around the world. We imagine we will satisfy you. We also warmly welcome shoppers to visit our organization and purchase our merchandise.
China High Quality megger resistance tester Factories – GDCR1000C Non-contact Phase Sequence Tester – HV Hipot Detail:

General Information

GDCR1000C, GDCR1000D non-contact phase tester is a major breakthrough in traditional phase sequence detection method. The traditional phase sequence detection is to strip the connection pole of three-phase wires, connect three bare clamps or test needles of phase sequence meter to three bare fire lines, while GDCR1000C and GDCR1000D adopt pincers non-contact induction measurement. The phase sequence can be detected by no need peeling off the wire and without touching the bare high-voltage fire wire, just directly clamping three super-inductive high-insulation clamps on the insulation skin of the three-phase fire wire respectively. At the same time, acousto-optic indication of the positive or reverse phase state of the phase sequence of the three-phase power supply can be obtained. There are four strong magnets on the back of the instrument, which can be attached to the distribution box for use.

GDCR1000C, GDCR1000D non-contact phase tester has the functions of looping inspection, simple power inspection, circuit breaking search, breakpoint location, line maintenance and so on.

GDCR1000C, GDCR1000D non-contact phase detector detection is fast, convenient and easy to display at a glance, greatly improving the safety of field testing, effectively protecting the personal safety of operators, and increasing productivity! It is a safety instrument for three-phase power supply phase sequence, motor detection and line maintenance.

GDCR1000C & GDCR1000D:

Model

Test wire outer diameter

GDCR1000C

ø1.6mm~ø16mm

GDCR1000D

ø10mm~ø40mm

Specification

Function Phase check(positive phase, reverse phase, missing phase), live line check, breakpoint location , line maintenance
Power supply DC 3V 2 section alkaline dry cell (LR6), continuous use time of about 70 hours
Live range AC 70~1000V, 45~65Hz (sine wave continuous input)
Test wire size Outer diameter ø1.6mm~ø16mm or ø10mm~ø40mm(optional)
LED display [positive phase] 4 phase detection lights turn on clockwise in turn;
[reverse phase] 4 phase detection lights turn on clockwise sequentially.
[live line] L1, L2 and L3 lights turn on within the range of voltage setting;
[missing phase] L1 or L2 or L3 lights are not on.
[open circuit] The L1 or L2 or L3 lights are not on.
Buzzing [positive phase] instrument emits intermittent short buzz;
[reverse phase] The instrument emits continuous long sounds.
Battery Indication POWER indicator lights up after power on; LOW BATTERY lights up when power is insufficient
Magnetism There are four magnets attached to the back of the instrument, which are attached to the distribution box and can withstand 800g quality.
Shut off After about 5 minutes, the instrument shuts down automatically.
Dimension L 70mm* H 75mm* W30mm
Clamp wire length 0.6m
Weight About 200g (include battery)
Working condition -10℃~55℃;<80%rh
Storage condition -20℃~60℃;<90%rh
Measurement max. voltage AC 1000V
Dielectric strength 5.4kV rms
Max. rated power 300mVA
Standards EN61010-1:2001, EN61010-031:2002, pollution class 2, CAT Ⅲ(600V), transient overvoltage 6000V

Accessories

Carry case 1pc
Battery (LR6) 2pcs
Packing list 1copy
User’s Guide 1copy
Factory test report 1copy

Product detail pictures:

China High Quality megger resistance tester Factories –  GDCR1000C Non-contact Phase Sequence Tester – HV Hipot detail pictures

China High Quality megger resistance tester Factories –  GDCR1000C Non-contact Phase Sequence Tester – HV Hipot detail pictures

China High Quality megger resistance tester Factories –  GDCR1000C Non-contact Phase Sequence Tester – HV Hipot detail pictures

China High Quality megger resistance tester Factories –  GDCR1000C Non-contact Phase Sequence Tester – HV Hipot detail pictures

China High Quality megger resistance tester Factories –  GDCR1000C Non-contact Phase Sequence Tester – HV Hipot detail pictures

China High Quality megger resistance tester Factories –  GDCR1000C Non-contact Phase Sequence Tester – HV Hipot detail pictures

China High Quality megger resistance tester Factories –  GDCR1000C Non-contact Phase Sequence Tester – HV Hipot detail pictures

China High Quality megger resistance tester Factories –  GDCR1000C Non-contact Phase Sequence Tester – HV Hipot detail pictures


Related Product Guide:

We also offer product sourcing and flight consolidation services. We've got our personal factory and sourcing office. We can easily present you with almost every style of merchandise linked to our merchandise range for China High Quality megger resistance tester Factories – GDCR1000C Non-contact Phase Sequence Tester – HV Hipot , The product will supply to all over the world, such as: Honduras, Italy, Albania, Customer satisfaction is our first goal. Our mission is to pursue the superlative quality, making continual progress. We sincerely welcome you to make progress hand in hand with us, and construct a prosperous future together.
  • Staff is skilled, well-equipped, process is specification, products meet the requirements and delivery is guaranteed, a best partner!
    5 Stars By Mabel from Uruguay - 2018.11.02 11:11
    Problems can be quickly and effectively resolved, it is worth to be trust and working together.
    5 Stars By Fernando from Oman - 2017.07.07 13:00

    Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us