Our solutions are broadly acknowledged and dependable by users and may meet consistently developing economic and social requires for Capacitor Discharge Device, Capacitor Testing Meter, Dc Resistance Test For Transformer, We will wholeheartedly welcome all clients in the industry both at home and abroad to cooperate hand in hand, and create a bright future together.
China High Quality Sf6 Breaker Maintenance Exporters – GDJD-3A SF6 gas Density Relay Calibrator – HV Hipot Detail:

Product Description

GDJD-3A SF6 gas Density Relay Calibrator is automatic calibrator, which uses embedded microprocessor to proceed performance calibration for all kinds of SF6 gas density relay. It is also a portable device which can make standard conversion for SF6 gas pressure at any environmental temperature. This device is mainly used for SF6 gas products production, maintenance and monitoring in power system.

Features

● Automatically calibrate density relay and pressure gauge.
● Compact design, small size, and light weight, easy to carry.
● Color LCD screen, Windows menu.
● The power supply has UPS function, suitable for field operation.
● With mini-printer, to print test result directly.
● Good sealing property, do not waste SF6 gas during calibration.
● The two ends of connection pipe has fast check valve, easy operation and avoid water and air entering into the pipe. No need to dismantle most of density relay to calibrate directly.
● There is automatic voltage protector for sampling point. If sampling point clip misconnecting with 220V voltage, it will not destroy device.  

Functions

Automatically measure pressure when SF6 gas density relay alarm or disalarm at any environmental temperature. It also can convert it to standard pressure at 20℃, to realize alarm performance calibration.

Automatically measure pressure when SF6 gas density relay interlock or relive interlock at any environmental temperature. It also can convert it to standard pressure at 20℃, to realize interlock performance calibration.

If there is pressure gauge or density meter of tested SF6 gas density relay, it can calibrate the accuracy of pressure gauge or density meter.

Convert the SF6 gas pressure into standard pressure at 20℃.

Convert the standard pressure at 20℃ into pressure at any temperature.

Set multiple measurement for one density relay. The measurement result is average value.

Specifications

Power supply: AC/DC use, built-in rechargeable battery, AC 220V±10%, 50Hz
Accuracy: Class 0.25
Display: 3.5inch true color LCD screen
Printer: Needle type microprinter
Measurement pressure range: 0-1.0Mpa
Calibration pressure range: standard pressure 0-0.9Mpa at 20℃
Temperature range: -50℃–100℃
Dimension: 258*240*88mm
Weight: about 2.5kg
Pressure resolution: 0.0001Mpa
Temperature resolution: 0.1℃
Storage capacity: 50-100pcs
Communication port: USB2.0


Product detail pictures:

China High Quality Sf6 Breaker Maintenance Exporters –  GDJD-3A SF6 gas Density Relay Calibrator – HV Hipot detail pictures

China High Quality Sf6 Breaker Maintenance Exporters –  GDJD-3A SF6 gas Density Relay Calibrator – HV Hipot detail pictures

China High Quality Sf6 Breaker Maintenance Exporters –  GDJD-3A SF6 gas Density Relay Calibrator – HV Hipot detail pictures

China High Quality Sf6 Breaker Maintenance Exporters –  GDJD-3A SF6 gas Density Relay Calibrator – HV Hipot detail pictures

China High Quality Sf6 Breaker Maintenance Exporters –  GDJD-3A SF6 gas Density Relay Calibrator – HV Hipot detail pictures

China High Quality Sf6 Breaker Maintenance Exporters –  GDJD-3A SF6 gas Density Relay Calibrator – HV Hipot detail pictures


Related Product Guide:

We've one of the most advanced generation tools, experienced and qualified engineers and workers, recognized good quality manage systems and a friendly skilled product sales workforce pre/after-sales support for China High Quality Sf6 Breaker Maintenance Exporters – GDJD-3A SF6 gas Density Relay Calibrator – HV Hipot , The product will supply to all over the world, such as: Mombasa, luzern, Japan, We've got sufficient experience in producing products according to samples or drawings. We warmly welcome customers from home and abroad to visit our company, and to cooperate with us for a splendid future together.
  • The company leader recept us warmly, through a meticulous and thorough discussion, we signed a purchase order. Hope to cooperate smoothly
    5 Stars By Christian from Czech Republic - 2018.07.27 12:26
    It's really lucky to find such a professional and responsible manufacturer, the product quality is good and delivery is timely, very nice.
    5 Stars By Gary from Adelaide - 2018.07.12 12:19

    Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us