The consumer fulfillment is our primary goal. We uphold a consistent level of professionalism, top quality, credibility and service for High Voltage Meter, Dissipation Factor Tan Delta, Voltage Tester, If you have the requirement for virtually any of our items, make sure you call us now. We are wanting ahead to hearing from you before long.
China High Quality Use Of Coupling Capacitor Factory – VLF AC Hipot Test Set – HV Hipot Detail:

Withstand voltage test is an essential preventive test for electrical equipment. It is divided into two parts: AC and DC withstand voltage test. AC test can be further divided into power frequency, variable frequency and 0.1Hz very low frequency test, among which the last one is highly recommended by IEC, due to its remarkable advantages.

Following is a comparison for DC, Power Frequency, Variable Frequency, and 0.1Hz test.

Aspects

DC

Power Frequency

Variable Frequency

0.1Hz

Equivalency

poor

good

good

good

Insulation Damage

strong

slight

slight

slight

Operation Safety

relatively low

relatively low

relatively low

high

Wiring Difficulty

complicated

complicated

most complicated

simple

Volume

smallest

largest

large

small

In fact VLF test is the substitute for power frequency test. It is suitable for testing electrical equipment with large capacitance (like power cable, power capacitor, motor, and generator).

Description

The new generation of VLF series 0.1Hz VLF AC Hipot Test Set developed by HV Hipot adopts “Smart Quick” intelligent power test system (Soft No. 1010215, trademark registration number 14684781), HV HIPOT company introduced the latest international power electronic components and the latest ARM7 microcontroller technology, further reducing the size and weight of the equipment. The operation is easier, and the performance is more stable.

Features

● Advanced technology adopts digital frequency conversion technology, fully automatic microcomputer control, voltage boost, step-down, measurement, protection, etc.
● Control part and High-voltage part adopt an integrated structure design, and only a high voltage wire and ground wire are needed to connect to the tested product without the intermediate connection wire.
● Trolley-style design is convenient for transportation in various working environments, and its small size and light weight are very conducive to outdoor operations(80kV).
● Over-voltage protection and over-current protection. Action time is no longer than 10ms.
● The control unit and the booster are connected at low voltage, with photoelectric isolation control, safe and reliable to use.
● Closed-loop negative feedback circuit is adopted. No capacity rising during outputting.
● Capacitive touch screen, LCD graphic display, automatic storage, and printing.
● 0.1Hz, 0.05Hz and 0.02Hz can be chosen, which ensures a wide test range.

Specifications

● Peak voltage: 30kV
● Test frequency: 0.1Hz, 0.05Hz and 0.02 Hz (selectable)
● Maximum load capacity: 1.1μF@0.1Hz   /   2.2μF@0.05Hz   /   5.5μF@0.02Hz
● Measurement accuracy: 3%.
● Voltage peak value error: ≤3%.
● Voltage waveform distortion: ≤5%.
● Working environment: indoor or outdoor; -10℃-+40℃; 85%RH
● Fuse: 8A (30kV)
● Power supply: 220V ±10%, 50Hz ±5% (If using a portable generator, make sure the output voltage and frequency are stable. Power >3kW, frequency 50Hz, voltage 220V±5%.)
● Capacitance of the tested object shall not exceed the max. rated capacitance of the instrument.


Product detail pictures:

China High Quality Use Of Coupling Capacitor Factory –  VLF AC Hipot Test Set – HV Hipot detail pictures

China High Quality Use Of Coupling Capacitor Factory –  VLF AC Hipot Test Set – HV Hipot detail pictures

China High Quality Use Of Coupling Capacitor Factory –  VLF AC Hipot Test Set – HV Hipot detail pictures

China High Quality Use Of Coupling Capacitor Factory –  VLF AC Hipot Test Set – HV Hipot detail pictures


Related Product Guide:

Our well-equipped facilities and great excellent command throughout all stages of generation enables us to guarantee total customer fulfillment for China High Quality Use Of Coupling Capacitor Factory – VLF AC Hipot Test Set – HV Hipot , The product will supply to all over the world, such as: Philippines, Madras, Plymouth, With nearly 30 years' experience in business, we are confident in superior service, quality and delivery. We warmly welcome customers from all over the world to cooperate with our company for common development.
  • It's really lucky to find such a professional and responsible manufacturer, the product quality is good and delivery is timely, very nice.
    5 Stars By Barbara from Venezuela - 2017.09.29 11:19
    This enterprise in the industry is strong and competitive, advancing with the times and develop sustainable, we are very pleased to have a opportunity to cooperate!
    5 Stars By Dale from Pakistan - 2017.02.14 13:19

    Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us