GDZG-S DC Hipot Test Set

GDZG-S DC Hipot Test Set

Brief Description:

GDZG-S series is equipment of testing DC voltage and DC leakage current of water-cooled generator in the situation of water through, which completely overcome the problems of long blow water time, bottom water hard to dry, easy to cause arcing within the coil. The device is light, simple wiring, and easy to read. Polarization compensation voltage is output directly by the case.


Product Detail

Product Tags

Features

Electronic control and tune, easy to operate.
The date of voltage and current are recorded in the panel, reading without conversion.
One minute timing and tip function.
Perfect overvoltage and over-current protection function inside, also zinc oxide overvoltage protection outside, which ensure safety of generator.
Both control unit and doubler packed with special shockproof aluminum alloy cabinet, easy to move.
Portable design, suitable for on-site testing.

Specifications

Items(kV/mA) parameter

50/100

50/120

60/150

60/200

60/300

Output voltage(kV)

50

50

60

60

60

Output current(mA)

100

120

150

200

300

Output power(W)

5000

6000

9000

12000

18000

Voltage measurement error

≤1.0% ±1digit

Current measurement error

≤1.0% ±1digit

Overvoltage setting error

≤1.0%

Ripple coefficient

≤3.0%

Voltage stability

≤1.0%

Power supply

AC220V

AC380V (three phase, four wire)

Control unit weight

25.0kg

25.0 kg

25.0kg

Doubler weight

45.0kg

65.0kg

70.0kg


  • Previous:
  • Next:

  • Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us