GD3127 Series High Voltage Insulation Resistance Tester
GD3127 Series Insulation Resistance Tester is widely used in maintenance of electrical equipment in transformer substation, power plant, etc. It is suitable for carrying out measurement of insulation resistance(IR), polarization index(PI), absorption ratio (DAR), ramp(RAMP), filter(FR, 10s, 20s, 30s, 40s 4 choices), voltage(V), current(nA) of all kinds of high voltage equipment, including switchgear, transformers, reactors, capacitors, motors, generators and cables, etc.
GD3127 Series is the perfect test tool for early identification and discovery of preventive or predictive maintenance plans for potential equipment failures. It is of great significance to ensure product quality and the safety of people and equipment in operation. The insulation performance of electrical products is one of the important signs to evaluate the insulation quality, which is reflected by the insulation resistance test.
● Max. short current >5mA.
● Insulation resistance(IR), polarization index(PI), absorption ratio(DAR).
● Ramp(RAMP), filter(FR), voltage(V).
● Automatically monitor the live voltage of the measured object, and automatically prohibit the test if the voltage exceeds 36V, which effectively protects the instrument and the operator.
● Timing function, automatic record the test time.
● Automatically discharge high voltage after measurement is completed, the discharge time is no more than 30 seconds.
● Automatic power off function.
● Large LCD screen dot matrix display with stable performance.
● Double-layer shell structure, sturdy and durable, protection grade IP65.
● Large capacity rechargeable lithium battery pack.
● Storage function, can automatically store 1000 sets of real-time test data with test date and time and test timing.
● Upload function, equipped with USB interface, record data can be uploaded to computer for statistical analysis of data.
Function | Insulation resistance(IR), polarization index(PI), absorption ratio (DAR), ramp(RAMP), filter(FR, 10s, 20s, 30s, 40s 4 choices), voltage(V), current(nA) |
Power supply | Rechargeable lithium battery 5.2Ah |
Rated voltage | GD3127: 250V, 500V, 1kV, 2.5kV, 5kV GD3127B: 250V, 500V, 1kV, 2.5kV, 5kV, 10kV |
Output voltage accuracy | (5%-10%) ±10V |
Insulation resistance measuring range | GD3127: 0.50MΩ~2.00TΩ GD3127B: 0.50MΩ~5.00TΩ |
Short circuit current | >5mA |
Polarization index(PI) | Yes |
Absorption ratio (DAR) | Yes |
Ramp(RAMP) test mode | Test in steps of 10% of the preset voltage until the preset voltage |
Filter test mode | Four choices of 10S, 20S, 30S, 40S |
Voltage test | Range: AC/DC 0V-1000V, accuracy:±5%rdg±3V |
Current test | Range: 0.01nA-7mA, accuracy:±5%rdg±0.5nA |
Voltage monitor | Monitor the voltage of the tested object, monitor the discharge state after the test, and prohibit the test when the voltage is greater than 36V, protect the instrument and the operator |
Test timer | Automatically record test time, timing range: 0s~9999s |
Storage | Automatic storage of test data with date and time, a total of 1000 groups |
Communication | Upload the stored test data to the computer through the USB communication line. |
Battery | There is a battery level display, reminding to charge in time when the battery voltage is low |
Auto power off function | Auto power off after 15 minutes |
Protection class | IP65/IP40 |
Insulation resistance | 50MΩ(1000V) (between test circuit and shell) |
Withstand voltage | AC 3kV 50Hz 1min (between test circuit and shell) |
Standards | IEC61010-1, IEC61326-1 |
Working temperature and humidity | - 20℃ ~ + 50℃ < 80%RH |
Storage temperature and humidity | - 25℃ ~ + 65℃ < 80%RH |
Power Supply | 220V AC 50Hz |
Dimension (mm) | 280 (L)*260(W)*160(H) |
Weight | 4400g(include battery) |
Insulation resistance tester | 1 set |
High voltage test wire (Red) | 1 piece |
Test wire(Green) | 1 piece |
Test wire(Black) | 1 piece |
Power adapter | 1 piece |
User's guide | 1 copy |
Test report | 1 copy |