GDPD-316M Handheld Partial Discharge Detector

GDPD-316M Handheld Partial Discharge Detector

Brief Description:

The GDPD-316M handheld Partial Discharge Detector uses smart quick intelligent power test system (Soft No. 1010215, trademark registration number 14684781). It can flexibly configure various sensors according to different products to be tested. TEV, ultrasonic and HFCT are suitable for partial discharge detection of high-voltage switchgear and ring network cabinet; Ultrasonic and UHF are suitable for detection of insulating status of GIS; Ultrasonic and HFCT are suitable for detection of insulating status of power cable. The built-in expert diagnosis system can analyze the test data and judge the discharge energy and possible parts. It is widely used in electric power and railway.


Product Detail

Product Tags

Features

Types of detection equipment: Applicable to transformer, reactor, ring network cabinet, switch cabinet, GIS high voltage cable, overhead line and other power equipment under different voltage levels of live discharge detection.

Simple field use, convenient operation, no power outage, no test source.
Detection function: transient earth voltage detection, UHF detection, HF current detection, built-in non-contact ultrasonic detection, external contact ultrasonic detection, external focused ultrasonic detection, external flexible ultrasonic detection.
Automatic inspection function: The instrument should have the RFID tag scanning function to achieve the information management of power equipment inspection work.
The device can carry out internal partial discharge on-line testing on the external surface of the high voltage equipment with its own shell such as dry transformer.
UHF detection mode and HF current detection mode have the following functions,
With amplitude detection mode, it can trigger continuously or single trigger collection to test dB value of partial discharge signal.
With periodic graph detection, display the phase distribution of the signal under simplex frequency period.
With PRPD, PRPS detection mode, real-time rolling display of the two-dimensional and three-dimensional map of the partial discharge signal.
The detection bandwidth of UHF signal can be selected in each detection mode, which can be divided into high-pass, low-pass and all-pass.
Ultrasonic detection mode has the following functions:
Amplitude detection mode: display the effective value, maximum value and frequency component information of ultrasonic signal.
Phase pattern: PRPD pattern showing ultrasonic signal.
Pulse pattern mode, display ultrasonic signal flight pattern.
Wave pattern mode, display the original waveform signal of ultrasonic signal, can display no less than 10 power frequency cycles of the time domain map display.
In the above detection mode, continuous and trigger detection can be carried out, the conversion between mV and dB can be carried out, and the amplification multiple can be adjusted.
The transient earth voltage detection (TEV) mode has the following functions:
With amplitude detection mode, can be triggered continuously or single trigger collection, test partial discharge signal dB value, with yellow, green, red to indicate the severity of discharge.
The number and severity of partial discharge pulses can be displayed.
Over warning value color display.
Data storage, built-in storage capacity is not less than 8G. The host can save the transient earth voltage (TEV), ultrasonic detection data and spectrum, and the detection data can be uniquely identified by the equipment information of the switch cabinet.
Headset sound monitoring, can monitor the ultrasonic signal, configure the headset.
With amplitude map, waveform mode, continuous mode, pulse mode, flight mode, cyclical diagram, phase diagram, waveform diagram, PRPS/PRPD diagram and other analysis methods, which can effectively judge the amplitude, type and severity of partial discharge.
With a variety of phase synchronization mode, internal synchronization, wireless power synchronization to make the instrument phase and field frequency phase consistent.
The whole machine has transient earth voltage, air ultrasonic, contact ultrasonic, UHF, HF current, RFID scanning six-in-one intelligent instrument.
With PRPS, PRPD spectrum intelligent color level function, can clearly identify multi-point discharge signals.
With yellow, green, red three colors to indicate the severity of discharge function.
With ultrasonic recording function, ultra-high frequency dynamic PRPS/PRPD spectrum recording function.
Data communication functions:
Support WIFI, 4G/3G network and other wireless communication methods.
The UHF sensor, the HF current sensor and the test host are connected wirelessly.
The host conducts direct data exchange with the supporting analysis software through the data line.
Data analysis software function:
Software is used to collect, query and analyze printing data, and provide a basis for judging the insulation state.
Software supports the management analysis of TEV, HF current, UHF detection data, ultrasonic value detection data, ultrasonic phase detection data, ultrasonic pulse detection data, ultrasonic detection data.
With typical diagnostic and fault diagnosis function.
The main functions of the software include data acquisition, test table generation and download, graph generation, saving graph as graph file and pdf document, graph printing, report generation and printing.
The software data graph can display device number, test time, trigger peak, synchronization mode, and phase offset information.

Specifications
PD signal acquisition host
Monitor 4.3inch 480 x 800 HD screen
Touch screen Capacitive screen
Operation method Touch/button
Communication method WIFI, Bluetooth, TYPC-C port
IT application Support RFID scanning
Synchronous mode Internal synchronization, power synchronization, optical synchronization
Memory capacity 8G
Port 3.5mm stereo headphone jack
Host size 181x107x36mm
Host weight 0.45kg
Power supply mode The built -in rechargeable lithium battery, the battery voltage is low, or the machine is automatically turned off when it is not operated for a long time
Charging mode Type-C port 5V/2A charging
Charge time ≤5 hours
Standby time ≥8 hours
Working environment Temperature: -5 ~ 55 ℃; Humidity: 0 ~ 90%
HFCT detection
Detection bandwidth 500K-50MHz
Transmission impedance >10mV/mA (10MHz)
Dynamic range 0~80dB
Accuracy 1dB
Measurement error ±1dB
Output mode BNC interface - Signal conditioning unit, wireless connection to the host
TEV detection
Frequency range 3~100MHz
Measurement range 0-60dBmV
Accuracy 1dB
Measurement error ±1dB
AE detection
Contact ultrasonic frequency range 20kHz-300kHz
Non-contact ultrasonic peak frequency 40kHz
Detection sensitivity 0.1mV
Measuring range 0.1mV1V
UHF detection
Frequency range 300~1500MHz
Measuring range 0~70dB
Controllable frequency band High pass, low pass, band pass
Accuracy 1dB
Measurement error ±1dB
Output mode BNC interface - Signal conditioning unit, wireless connection to the host
Configuration table
No. Model No. Product name Unit Quantity

Remark

1 GDPD-316M Handheld partial discharge detector Set 1 One-piece handheld unit (built-in AA, TEV sensor) + external contact ultrasonic + wireless UHF sensor + wireless high frequency HFCT sensor + wireless external power synchronization function +RFID function + external headset five-in-one sensor
2 GDPD-316S Switch cabinet partial discharge detector Set 1 One-piece handheld unit (built-in AA and TEV sensor) + wireless external power synchronization function +RFID function + external headset two-in-one sensor
3 GDPD-316U Transformer partial discharge detector Set 1 One-piece hand-held unit (host built-in AA, TEV sensor) + external contact type ultrasonic + high frequency HFCT wireless sensor + wireless functions of external power synchronous + RFID + external headset Four one sensor
4 GDPD-316G GIS partial discharge detector Set 1 One-piece handheld unit (built-in AA, TEV sensor) + external contact ultrasonic + wireless UHF sensor + wireless external power synchronization function +RFID function + external headset four-in-one sensor
5 GDPD-316C Cable partial discharge detector Set 1 One handheld unit (built-in AA and TEV sensors) + wireless high frequency HFCT sensor + wireless external power synchronization function +RFID function + external headset three-in-one sensor
Accessories
Handheld partial discharge detector 1 piece

 

TEV sensor (built-in)

 

1 piece

 

AA Air sound sensor (built-in)

 

1 piece

 

UHF sensor (optional)

 

1 piece

 

HFCT sensor (optional)

 

1 piece

 

External AE contact ultrasonic sensor (optional)

 

1 piece

 

Wireless UHF signal adjuster (optional)

 

1 piece

 

Wireless HFCT signal adjuster (optional)

 

1 piece

 

Wireless synchronous signal transmitter

 

1 piece

 

Headphone

 

1 piece

 

Sensor and signal conditioning box N-BNC connection line(optional)

 

2 pieces

 

Host charger (5V/2A) with data line

 

1 piece

 

Coupling agent(optional)

 

1 box

 

Operation Manual

 

1 copy

 

Accessory case

 

1 piece

 

Optional item:

 

Parabolic sensor 1 piece

 

Extended ultrasound sensor 1 piece

 

Carry case of parabolic sensor 1 piece

 


  • Previous:
  • Next:

  • Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us