OEM Best 100 Kv Capacitor Suppliers – 30kVA.200kV Automatic AC.DC Hipot Test Set GDYD-2030A – HV Hipot
OEM Best 100 Kv Capacitor Suppliers – 30kVA.200kV Automatic AC.DC Hipot Test Set GDYD-2030A – HV Hipot Detail:
Features
● 7inch color LCD screen, with PLC automation control.
● HV Voltage, LV voltage, LC current measured at the same time, with high precision sensor and high-performance collection chip.
● Automatic mode and manual mode for option.
● Display HV voltage, LV voltage, LV current, time, and withstanding result.
● Over-voltage and over-current protection. Output voltage, HV current upper limit, LV current upper limit and timing can be set.
● Zero-starting function. Test can be proceeded after the voltage is back to zero.
● Store up to 8000pcs data in 3months. It has USB port to upload data to USB disk.
● When setting voltage is arrived, it will be timing automatically. After timing, voltage will be back to zero.
● When the LV current is over setting value, the voltage will be cut off automatically and it will be back to zero. When the HV current is over setting value, the test object will be cut off and test can be proceeded continuously.
● With anti-interference ability, suitable for electromagnetic environment.
● With wheels for both control unit and HV unit, easy to move.
Technical Specifications
Control unit specifications
● Power: AC380V, 50/60Hz
● Capacity: 30kVA
● Output voltage: AC 0-430V
● Rated output current: 75A
● Rated current rectified range: 0-75A
● HV voltmeter range: 0-200kV
● Accuracy: 1.5% of the reading±1digit (F.S)
● HV ammeter range: 0-100mA
● Accuracy: 1.5% of the reading±1digit (F.S)
● LV ammeter range: 0-25A
● Accuracy: 2.0% of the reading±1digit (F.S)
● Timing range: 1s-99h
● Weight: about 116kg
● Dimension: 520mm (L)*460mm (W)*1140mm (H)
Testing transformer (HV unit) specifications
● Input voltage: 0-400V
● Input current: AC 0-75A
● Output voltage: AC 0-200kV, DC 0-200kV
● Output current: AC 150mA, DC 106mA
● Capacity: 30kVA
● HV side/LV side turns ratio: 500:1
● Measuring voltage: AC 0-100V
● Accuracy: 1.5% of the reading±1 digit (F.S)
● No-load current: <10%
● Impedance voltage: <10%
● Weight: about 180kg
● Dimension: 630mm(D)*1730mm(H)
Working conditions
● Working place: No gas, steam, chemical dust and explosive and corrosive medium which will influence insulation.
● Environment temperature: -20–50℃.
● Environment humidity: ≤85% RH (no condensing).
Product detail pictures:
Related Product Guide:
We support our purchasers with ideal high-quality merchandise and significant level company. Becoming the specialist manufacturer in this sector, we now have received loaded practical encounter in producing and managing for OEM Best 100 Kv Capacitor Suppliers – 30kVA.200kV Automatic AC.DC Hipot Test Set GDYD-2030A – HV Hipot , The product will supply to all over the world, such as: Birmingham, Denmark, Pakistan, With well educated, innovative and energetic staff, we are responsible for all elements of research, design, manufacture, sale and distribution. By studying and developing new techniques, we are not only following but also leading fashion industry. We listen attentively to the feedback from our customers and provide instant replies. You will instantly feel our professional and attentive service.
By Ryan from French - 2018.12.05 13:53
High production efficiency and good product quality, fast delivery and completed after-sale protection, a right choice, a best choice.
By Ella from belarus - 2018.12.14 15:26