OEM Best distribution transformer and power transformer Supplier – GDJF-2008 Partial Discharge Analyzer – HV Hipot
OEM Best distribution transformer and power transformer Supplier – GDJF-2008 Partial Discharge Analyzer – HV Hipot Detail:
GDJF-2008 Partial Discharge Detector is measuring partial discharge for the products such as transformers, mutual inductors, HV switches, zinc monoxide arresters and power cables. It also can make type tests and monitor insulation operation.
This type has the advantages of high sensitivity, wide range of capacitance, being well equipped for input unit impedance detecting and more variants of frequency bands (9 in all). After proper setting, the discharge impulse amount can be read directly. The indicating and digital meters are shown simultaneously.
This detector is widely applied in power stations, manufacturers, and institutions.
Use Condition
● Ambient temperature: 0-40℃±2℃.
● Relative humidity: ≤80%
● Power supply: 220V±10%, 50HZ.
● No violent vibration and mechanical shock.
● The device should be placed in the environment with no dust and corrosive, good ventilation. It should not be interfered by strong electromagnetic.
● Earthing requirements: earthing resistance <1Ω.
● Capacitance range to be tested 6PF-250μF.
● Testing sensitivity (shown in Table.1).
Input unit No. |
Tuning capacitance |
Unit |
Sensitivity(pC) (Unsymmetrical circuit) |
1 |
6-25-100 |
pF |
0.02 |
2 |
25-100-400 |
pF |
0.04 |
3 |
100-400-1500 |
pF |
0.06 |
4 |
400-1500-6000 |
pF |
0.1 |
5 |
1500-6000-25000 |
pF |
0.2 |
6 |
0.006-0.025-0.1 |
mF |
0.3 |
7 |
0.025-0.1-0.4 |
mF |
0.5 |
8 |
0.1-0.4-1.5 |
mF |
1 |
9 |
0.4-1.5-6.0 |
mF |
1.5 |
10 |
1.5-6.0-25 |
mF |
2.5 |
11 |
6.0-25-60 |
mF |
5 |
12 |
25-60-250 |
mF |
10 |
7R |
Resistance |
|
0.5 |
● Amplifier band
Low terminal: 10KHZ, 20 KHZ, 40 KHZ (optional)
High terminal: 80 KHZ, 200 KHZ, 300 KHZ (optional)
● Amplifier gain adjustment
Coarse control – there are 6 gears for coarse tuning, the gain of each gear is 20±1db
Fine control ≥ 20 db
● Time windows
Width of window, adjustable 15o—150o
Window position, adjustable 0o—170o
Two windows can be opened simultaneously or separately.
● Discharge meter
Digital display
PD display: LED 3½ digits
0-100.0 limit of error <±3% (full scale)
● Ellipse time base
Frequency: 50Hz and arbitrary frequency
Elliptic display color is yellow
Elliptic rotation: each gear is 30°, 180 ° rotation can be made.
Display: ellipse – straight line
High frequency time base elliptical input voltage less than 220 V, intake power < 1 VA
● Waveform lock
Lock required waveform of any time to facilitate observation and analysis
● Testing Voltage meter
Range: 100KV (Can be expanded)
Display 31/2 digital voltage meter
Accuracy: better than ±2% (full scale)
● Inside, outside the zero-mark function
● Dimensions: 450×450×190 mm
● Weight: about 16kg
Product detail pictures:


Related Product Guide:
Our target should be to consolidate and enhance the top quality and service of current goods, in the meantime frequently create new products to satisfy diverse customers' calls for for OEM Best distribution transformer and power transformer Supplier – GDJF-2008 Partial Discharge Analyzer – HV Hipot , The product will supply to all over the world, such as: Honduras, Rio de Janeiro, Australia, Immediate and specialist after-sale service supplied by our consultant group has happy our buyers. Detailed Info and parameters from the merchandise will probably be sent to you for any thorough acknowledge. Free samples may be delivered and company check out to our corporation. n Morocco for negotiation is constantly welcome. Hope to get inquiries type you and construct a long-term co-operation partnership.

Wide range, good quality, reasonable prices and good service, advanced equipment, excellent talents and continuously strengthened technology forces,a nice business partner.
