OEM Best instrument transformer Exporters – GDJF-2008 Partial Discharge Analyzer – HV Hipot

OEM Best instrument transformer Exporters – GDJF-2008 Partial Discharge Analyzer – HV Hipot

Brief Description:


Product Detail

Product Tags

Related Video

Feedback (2)

We continue to keep increasing and perfecting our solutions and service. At the same time, we operate actively to do research and enhancement for Online Pd Spot Tester, Online Pd Test, Surge Generator For Motor, We warmly welcome friends from all walks of existence to cooperate with us.
OEM Best instrument transformer Exporters – GDJF-2008 Partial Discharge Analyzer – HV Hipot Detail:

GDJF-2008 Partial Discharge Detector is measuring partial discharge for the products such as transformers, mutual inductors, HV switches, zinc monoxide arresters and power cables. It also can make type tests and monitor insulation operation.
This type has the advantages of high sensitivity, wide range of capacitance, being well equipped for input unit impedance detecting and more variants of frequency bands (9 in all). After proper setting, the discharge impulse amount can be read directly. The indicating and digital meters are shown simultaneously.
This detector is widely applied in power stations, manufacturers, and institutions.

Use Condition

● Ambient temperature: 0-40℃±2℃.
● Relative humidity: ≤80%
● Power supply: 220V±10%, 50HZ.
● No violent vibration and mechanical shock.
● The device should be placed in the environment with no dust and corrosive, good ventilation. It should not be interfered by strong electromagnetic.
● Earthing requirements: earthing resistance <1Ω.
● Capacitance range to be tested 6PF-250μF.
● Testing sensitivity (shown in Table.1).

Input unit No.

Tuning capacitance

Unit

Sensitivity(pC) (Unsymmetrical circuit)

1

6-25-100

pF

0.02

2

25-100-400

pF

0.04

3

100-400-1500

pF

0.06

4

400-1500-6000

pF

0.1

5

1500-6000-25000

pF

0.2

6

0.006-0.025-0.1

mF

0.3

7

0.025-0.1-0.4

mF

0.5

8

0.1-0.4-1.5

mF

1

9

0.4-1.5-6.0

mF

1.5

10

1.5-6.0-25

mF

2.5

11

6.0-25-60

mF

5

12

25-60-250

mF

10

7R

Resistance

 

0.5

● Amplifier band
Low terminal: 10KHZ, 20 KHZ, 40 KHZ (optional)
High terminal: 80 KHZ, 200 KHZ, 300 KHZ (optional)

Amplifier gain adjustment
Coarse control – there are 6 gears for coarse tuning, the gain of each gear is 20±1db
Fine control ≥ 20 db

Time windows
Width of window, adjustable 15o—150o
Window position, adjustable 0o—170o
Two windows can be opened simultaneously or separately.

Discharge meter
Digital display
PD display: LED 3½ digits
0-100.0 limit of error <±3% (full scale)

Ellipse time base
Frequency: 50Hz and arbitrary frequency
Elliptic display color is yellow
Elliptic rotation: each gear is 30°, 180 ° rotation can be made.
Display: ellipse – straight line
High frequency time base elliptical input voltage less than 220 V, intake power < 1 VA

Waveform lock
Lock required waveform of any time to facilitate observation and analysis

Testing Voltage meter
Range: 100KV (Can be expanded)
Display 31/2 digital voltage meter
Accuracy: better than ±2% (full scale)

Inside, outside the zero-mark function
● Dimensions: 450×450×190 mm
● Weight: about 16kg


Product detail pictures:

OEM Best instrument transformer Exporters –  GDJF-2008 Partial Discharge Analyzer – HV Hipot detail pictures

OEM Best instrument transformer Exporters –  GDJF-2008 Partial Discharge Analyzer – HV Hipot detail pictures


Related Product Guide:

It is a great way to further improve our products and repair. Our mission is always to create innovative products to prospects with a superior expertise for OEM Best instrument transformer Exporters – GDJF-2008 Partial Discharge Analyzer – HV Hipot , The product will supply to all over the world, such as: Portugal, Kyrgyzstan, Peru, Our well-equipped facilities and excellent quality control throughout all stages of production enable us to guarantee total customer satisfaction. If you are interested in any of our products or would like to discuss a custom order, please feel free to contact me. We are looking forward to forming successful business relationship with new clients around the world.
  • The company comply with the contract strict, a very reputable manufacturers, worthy a long-term cooperation.
    5 Stars By Andy from Southampton - 2018.06.28 19:27
    The customer service staff's attitude is very sincere and the reply is timely and very detailed, this is very helpful for our deal,thank you.
    5 Stars By Antonio from Malaysia - 2017.06.22 12:49

    Send your message to us:

    Write your message here and send it to us

    Send your message to us:

    Write your message here and send it to us