OEM Best megger insulation tester price Exporters – GDHX-9500 Phase Detector – HV Hipot
OEM Best megger insulation tester price Exporters – GDHX-9500 Phase Detector – HV Hipot Detail:
General Information
GDHX-9500 Phase Detector is mainly used in electric power lines, phase and phase sequence calibration in substation, with main functions including electrical inspection, phase calibration and phase sequence measurement. It uses double shielding and brand new digital circuits, with strong anti-interference, accorded with EMC standards, suitable for various electromagnetic interference situations.
The high voltage phase signal of measured lead will be transmitted directly after treatment, the handset will receive and make phase comparison, determine the results after phase detection, real-time display phase angle difference and vector.It uses wireless transmission technology, safe and reliable, fast and accurate, suitable for using at different voltage levels (6V-500KV). When checking the grid structure, it is able to accurately identify the relative phase of different leads for the three-phase connected line, without any electrical connection between two measurement components, which makes the application of the measurement device very flexible and safe.
Security Matters
● Using wireless transmission technology, its basic working principle is real-time phase comparison.
● Please observe and follow the regulation to use this product, in order to ensure the safe operation of the instrument, the ends of X and Y detector are not allowed to make withstand voltage test.
● The metal head parts of the insulating rod is strictly prohibited to contact with any objects during the test.
● Please comply with the national power industry safety regulations of preventive test for safety tools and products.
● Please pay attention to the training and examination for staffs who work on high-voltage live lines or near the high-voltage lines.
● Phase calibration on live equipment must be carried out by insulating rod.
Note: The safe usage length and test standards of insulating rod for “Wireless Phase Detector”.
(Excerpting from “Electrical safety working regulations of State Grid Corporation”.)
1. Safety distance between staff and the charged body during live operation.
Voltage Level |
10kV |
35kV |
66kV |
110kV |
220kV |
330kV |
500kV |
Safety Distance |
0.4M |
0.6M |
0.7M |
1.0M |
1.8M |
2.2M |
3.4M |
2. The minimum effective insulation length of insulating rod during live operation.
Voltage Level |
10kV |
35kV |
66kV |
110kV |
220kV |
330kV |
500kV |
Min. effective insulation length |
0.7M |
0.9M |
1.0M |
1.3M |
2.1M |
3.1M |
4.0M |
Note: The test standard of insulating tools checking test (subsection): applying power frequency 75kV each 300mm for 1min, if no breakdown, no flashover and over-heat, it is considered as qualify.
Features
● Test voltage: 10V-500kV, suitable for different voltage level.
● Accuracy: self-calibrating error ≤±3°.
● Sampling speed: 10 times/s.
● Date and time setting: date and time adjustment, easy for users to browse, view the historical data.
● Back-light time setting: normally on, normally off, 0-999s can be set by user.
● Auto power off setting: 0-999mins can be set by user.
● In-phase: ≤20° is considered as in-phase (phase threshold within 0-90°, can be set by user. The system default is 20°.)
● Out-phase qualitative: >20° (phase threshold within 0-90°, can be set by user. The system default is 20°.)
● Field calibration function: on-site calibration for measured lead, ensure the accuracy of phase angle.
● Transmission distance between handset and X, Y detector: X≤150m, Y≤150m.
● Multiple mode design, with strong applicability, safer and more convenient.
● Unique human-computer interaction interface, simple operation.
● FCC antenna design, the signal is stronger and easier to penetrate the blocking of wall, door, or barrier.
● Double shielding, strong an-ti interference, in full accordance with EMC standards.
● Charts and data display, more convenient and easier to read.
● Qualitative measurement, display by sound and light signal.
● Quantitative measurement, real-time display phase angle difference, error≤5°.
● Phase sequence calibration, positive phase sequence, negative phase sequence (120°, 240°).
Specifications
Test voltage |
10V-500kV |
Power supply |
Handset: No.5 AA alkaline battery 2 sections (1.5V) |
X and Y detector: No.7 AA alkaline battery 2 sections (1.5V) |
|
Wireless transmission distance |
Visual distance 150m |
In-phase |
Phase angle deviation≤20° (threshold within 0-90°, can be set by user self. ) |
Out-phase |
Phase angle deviation>20° (threshold within 0-90°, can be set by user self. ) |
Display accuracy |
Quantitative measurement≤3° |
Phase angle resolution |
1° |
Phase sequence measurement |
Through 120° clockwise/240°anti-clockwise to determine and indicate phase sequence |
Display |
Positive display LCD, clearly display under the sunshine |
Operation temperature |
-35℃-+50℃ |
Storage temperature |
-40℃-+55℃ |
Relative humidity |
≤95% RH, Non-condensate |
Handset |
0.31kg |
X detector |
0.13kg |
Y detector |
0.13kg |
Product detail pictures:
Related Product Guide:
"Based on domestic market and expand overseas business" is our development strategy for OEM Best megger insulation tester price Exporters – GDHX-9500 Phase Detector – HV Hipot , The product will supply to all over the world, such as: Argentina, Denmark, Canberra, We have been making our products for more than 20 years . Mainly do wholesale , so we have the most competitive price , but highest quality. For the past years , we got very good feedbacks , not only because we provide good products , but also because of our good after-sale service . We are here waiting for you for your inquiry.
By Renata from Guatemala - 2017.02.28 14:19
The factory has advanced equipment, experienced staffs and good management level, so product quality had assurance, this cooperation is very relaxed and happy!
By Aaron from Austria - 2017.03.07 13:42