OEM Best Testing Of Current Transformer Manufacturer – GDHG-106B CT/PT Analyzer – HV Hipot
OEM Best Testing Of Current Transformer Manufacturer – GDHG-106B CT/PT Analyzer – HV Hipot Detail:
Features
● Finish all testing items by itself, no need to connect auxiliary equipment.
● Intelligent controller is adopted.
● Built-in printer, to print results easily.
● Large screen LCD, graphically display.
● Auto display excitation knee point value, 5% and 10% error curve.
● Save 3000 groups data and it is not lost after power down.
● With USB port. The data can be saved in USB disk and read by PC (WORD format file).
● Portable design, suitable for on-site test.
● Engineering plastic box with damping, strong and reliable.
Specifications
Main functions
CT (protection type, metering type) | PT |
Voltage current characteristic curve (excitation characteristic) | Voltage current characteristic curve (excitation characteristic) |
Auto calculate knee point value | Auto calculate knee point value |
Auto display 5% and 10% error curve | Turns ratio measurement |
Turns ratio measurement | Polarity determination |
Ratio error measurement | Ratio error measurement |
Phase measurement (angular difference) | Phase measurement (angular difference) |
Polarity determination | AC withstand test |
Primary current injection test | Secondary winding resistance measurement |
AC withstand test | Secondary burden measurement |
Secondary winding resistance measurement | |
Secondary burden measurement | |
Fast Test (Iron core demagnetization comprehensive test, complete excitation, ratio and polarity test at one time) |
Main parameters
Item | Parameter | |
Power supply | AC220V±10%, 50Hz | |
Output | 0-2500Vrms, 5Arms (20A peak) | |
Output current | 0-1000A | |
Accuracy of excitation | ≤0.5%(0.2% of the reading+0.3% of the range) | |
Secondary winding resistance measurement | Range | 0.1-300Ω |
Accuracy | ≤1.0% (0.4% of the reading+0.6% of the range) | |
Secondary actual burden measurement | Range | 5-500VA |
Accuracy | ≤0.5% (0.2% of the reading+0.3% of the range) ±0.1VA | |
Angular error measurement | Accuracy | 4min |
Resolution | 0.1min | |
CT ratio measurement | Range | ≤25000A/5A (5000A/1A) |
Accuracy | ≤0.5% (0.2% of the reading+0.3% of the range) | |
PT ratio measurement | Range | ≤500KV |
Accuracy | ≤0.5% (0.2% of the reading+0.3% of the range) | |
Operation environment | Temperature: -10℃-40℃, Humidity: ≤90%, Altitude: ≤1000m | |
Dimension & Weight | Dimension: 345mm × 445mm × 380mm Weight: about 30kg |
Product detail pictures:
Related Product Guide:
We've got a specialist, effectiveness staff to supply high quality service for our shopper. We always follow the tenet of customer-oriented, details-focused for OEM Best Testing Of Current Transformer Manufacturer – GDHG-106B CT/PT Analyzer – HV Hipot , The product will supply to all over the world, such as: Cyprus, Brasilia, Cape Town, We are proud to supply our products to every auto fan all around the world with our flexible, fast efficient services and strictest quality control standard which has always approved and praised by customers.
By Mag from Saudi Arabia - 2017.06.25 12:48
Managers are visionary, they have the idea of "mutual benefits, continuous improvement and innovation", we have a pleasant conversation and Cooperation.
By Athena from Spain - 2018.02.08 16:45
Send your message to us:
Write your message here and send it to us