OEM Best Vlf Hipot Suppliers – 30kVA.200kV Automatic AC.DC Hipot Test Set GDYD-2030A – HV Hipot
OEM Best Vlf Hipot Suppliers – 30kVA.200kV Automatic AC.DC Hipot Test Set GDYD-2030A – HV Hipot Detail:
Features
● 7inch color LCD screen, with PLC automation control.
● HV Voltage, LV voltage, LC current measured at the same time, with high precision sensor and high-performance collection chip.
● Automatic mode and manual mode for option.
● Display HV voltage, LV voltage, LV current, time, and withstanding result.
● Over-voltage and over-current protection. Output voltage, HV current upper limit, LV current upper limit and timing can be set.
● Zero-starting function. Test can be proceeded after the voltage is back to zero.
● Store up to 8000pcs data in 3months. It has USB port to upload data to USB disk.
● When setting voltage is arrived, it will be timing automatically. After timing, voltage will be back to zero.
● When the LV current is over setting value, the voltage will be cut off automatically and it will be back to zero. When the HV current is over setting value, the test object will be cut off and test can be proceeded continuously.
● With anti-interference ability, suitable for electromagnetic environment.
● With wheels for both control unit and HV unit, easy to move.
Technical Specifications
Control unit specifications
● Power: AC380V, 50/60Hz
● Capacity: 30kVA
● Output voltage: AC 0-430V
● Rated output current: 75A
● Rated current rectified range: 0-75A
● HV voltmeter range: 0-200kV
● Accuracy: 1.5% of the reading±1digit (F.S)
● HV ammeter range: 0-100mA
● Accuracy: 1.5% of the reading±1digit (F.S)
● LV ammeter range: 0-25A
● Accuracy: 2.0% of the reading±1digit (F.S)
● Timing range: 1s-99h
● Weight: about 116kg
● Dimension: 520mm (L)*460mm (W)*1140mm (H)
Testing transformer (HV unit) specifications
● Input voltage: 0-400V
● Input current: AC 0-75A
● Output voltage: AC 0-200kV, DC 0-200kV
● Output current: AC 150mA, DC 106mA
● Capacity: 30kVA
● HV side/LV side turns ratio: 500:1
● Measuring voltage: AC 0-100V
● Accuracy: 1.5% of the reading±1 digit (F.S)
● No-load current: <10%
● Impedance voltage: <10%
● Weight: about 180kg
● Dimension: 630mm(D)*1730mm(H)
Working conditions
● Working place: No gas, steam, chemical dust and explosive and corrosive medium which will influence insulation.
● Environment temperature: -20–50℃.
● Environment humidity: ≤85% RH (no condensing).
Product detail pictures:


Related Product Guide:
Our corporation puts emphasis about the administration, the introduction of talented staff, plus the construction of team building, attempting hard to improve the quality and liability consciousness of team members. Our organization successfully attained IS9001 Certification and European CE Certification of OEM Best Vlf Hipot Suppliers – 30kVA.200kV Automatic AC.DC Hipot Test Set GDYD-2030A – HV Hipot , The product will supply to all over the world, such as: Moscow, New York, Swaziland, They are sturdy modeling and promoting effectively all over the world. Never ever disappearing major functions within a quick time, it's a have to in your case of fantastic good quality. Guided by the principle of Prudence, Efficiency, Union and Innovation. the corporation. ake an excellent efforts to expand its international trade, raise its organization. rofit and raise its export scale. We've been confident that we've been going to have a bright prospect and to be distributed all over the world in the years to come.

The quality of the products is very good, especially in the details, can be seen that the company work actively to satisfy customer's interest, a nice supplier.
