OEM Best Wire Tracer Exporters – GD-4138H Cable Fault Locating System – HV Hipot
OEM Best Wire Tracer Exporters – GD-4138H Cable Fault Locating System – HV Hipot Detail:
GD-4138H Mobile Cable Fault Locating System is important tool to maintain all kinds of cables. It is compatible equipment that can trace, locate the underground cables, with fault distance measurement and HV generation. As it is movable device, it is convenient to carry on-site. If acoustic locator is used together, it can locate accurate position of cable fault point.
Application is underground cable, aerial cable, power cable, local cable, communication cable and fiber cable.
Typical fault to be detected includes
● High impedance flash-over fault
● High impedance leak
● High/low resistive grounding
● Short-circuit fault
● Open-circuit fault
● Poor connection/Disconnection
GD-4138L system includes
● GD-4138H main frame (Coupling device, Sphere gap, HV generator are inside)
● GD-4133 Multiple pulse cable fault tester
● GD-4132 Cable Fault Locator
Features
● Multiple ranging methods: low-voltage pulse method, pulse current method, multiple pulse method: current sampling, DC output.
● Sampling signal types: DC arc reflection method, current sampling, voltage sampling, low voltage pulse.
● Quickly locate and point the low-resistance, high-resistance leakage faults and flashover faults of various 220V~220KV voltage grade power cables.
● There is no need to carry out complex wiring for on-site testing. All test modes are switched automatically through the internal high voltage switch controlled by the weak current.
● Integrated multi-speed DC high-voltage generator, multi-speed high-voltage capacitor, arc stabilizing unit and various signal acquisition in one, easy to operate fault location system.
● Multi-level output high voltage switching, all controlled by internal low voltage weak current, safe and reliable.
● The structure of the equipment adopts a high-strength plastic case. The case is the outer box of the equipment and the transfer box for the equipment delivery package. It is convenient to transfer, and it can be loaded and transferred directly when the cover is closed.
● Sphere gap impulse discharge: Weak current control solenoid valve air gap, the discharge period is adjustable from 3 to 12 seconds, and the muffler is specially designed to meet the requirements of mute for cable failure at the beginning.
● The equipment has a built-in discharge circuit. After the fault test is completed, the high voltage can be turned off just press the button at the discharge position to discharge automatically.
● The distance measuring host can provide a distance measuring resolution up to 0.4m, and the measurement blind area is small, which is particularly effective for near-end faults and short cables.
● All output terminals of the equipment are arranged on a rear panel for easy wiring, and wiring diagrams of various wiring methods are drawn on the operation panel, which can be easily used by people without experience.
● The bottom of the equipment is equipped with 4 high-strength sliding wheels, which can be pushed and stacked for storage.
● The ranging host uses a 7-inch large-screen LCD with a 160° viewing angle, and the display content is rich and intuitive.
● A large number of waveforms can be stored in the host, and the waveform data can be imported and exported using U disk.
● The host can be connected to a computer (desktop or notebook) for online communication.
● When the host has no operation within 2 minutes, the backlight will be weakened; if there is no operation for 10 minutes, it will automatically shut down to reduce power consumption; when the battery is undervoltage, the instrument will also automatically shut down to protect the battery.
● The host has a built-in polymer lithium-ion battery and is equipped with a dedicated lithium battery charger to provide a reliable charging method.
● The whole machine adopts an integral transfer box structure design, which is compact and firm, especially suitable for construction site use.
Specifications
Model | GD-4138L | GD-4138M | GD-4138H |
Test mode | Arc reflection method, current sampling, DC output | Arc reflection method, DC arc reflection method, current sampling, DC output | |
Ranging sampling signal type | Multiple pulse arc reflection method, current sampling, low voltage pulse | Arc reflection method, DC arc reflection method, current sampling, DC output | |
DC HV output | 0~16KV negative polarity Maximum output current: 152mA |
0~32KV negative polarity Maximum output current: 76mA |
0~8KV negative polarity Maximum output current: 304mA 0~16KVnegative polarity Maximum output current: 152mA 0~32KVnegative polarity Maximum output current: 76mA |
Flashover capacitance | 0-16kV 8μF Maximum output energy: 1024J |
0-32kV 4μF Maximum output energy: 2048J | 0-8kV 32μF Maximum output energy: 1024J 0-16kV 8μF Maximum output energy: 1024J 0-32kV 4μF Maximum output energy: 2048J |
Automatic sphere gap discharge | Weak current control solenoid valve air gap, the discharge period is adjustable from 3 to 12 seconds, and the muffler is specially designed to meet the requirements of mute for cable failure at the beginning. | ||
Output mode | DC withstand voltage, single discharge, periodic discharge | ||
DC withstand voltage | 16KV | 32KV | 32KV |
Allowable input impulse voltage | 16kV | 32kV | 32kV |
Allowable input impulse energy | <2048J | ||
Working environment | Temperature: 0~40℃ Relative humidity: <75%RH |
||
Power supply | AC220V, 50Hz | ||
Total capacity | 3kVA |
GD-4133 Multiple Pulse Cable Fault Tester
It is used to measure fault distance. Under LV pulse mode, it can be used alone.
7inch LCD screen, friendly interface.
Multiple distance locating method:
Low voltage pulse method: it is suitable for the locating of the low resistance fault, short circuit fault, open circuit fault. It also can be used in the measurement of the cable length, the intermediate joints, T joints, and cable termination joint. This method also can be used to correct the wave velocity.
Pulse current method: It is suitable for distance measurement of the high resistance fault, breakdown fault. Using the current coupler to collect signals from the earth wire, it makes the user far away from the high voltage. This method is safe and reliable.
Multiple pulse: the advanced way to measure distance. The waveform is easy to identify and the accuracy is high.
200MHz real-time sampling. Max. 0.4m measurement resolution. It has small dead zone and is special for the short cable and near fault cable.
Touch screen and press key operation. The cursor can be dragged.
PIP copy(pic. temporary storage)
There will be a main window and three temporary storage windows could check three waveforms together.
Built-in embedded operating system
Special software management for software upgrade, backup and restore.
Scale function
One starting point,10 contacts, one cable fault and one full length could be setting.
Display scale and testing waveform at the same time
Waveform storage and communication with computer.
Internal storage of waveforms.
With USB, to download or upload data
Communication with computer
Power management
Backlight weakens if no operation in 2mins and power off in 10mins if no operation.
Built-in Polymer Lithium-ion battery.
Working time is up to 5 hours for each use.
Strong case, easy to carry.
Specifications
Locating methods |
Low voltage impulse method Impulse current method Multiple impulse method |
Max. Sampling frequency |
200MHz |
Gain range |
0-70dB |
Low voltage impulse voltage |
30V |
Max.resolution |
0.4m |
Max. Locating range |
100km |
Dead zone |
2m |
Battery |
Nickel-metal hydride rechargeable batteries, endurance time over 5 hours |
Communication interface |
USB |
Power supply |
Input AC220V, 50Hz, current 2A, charge for 8 hours |
Dim. |
274×218×81mm |
Weight |
3.5kg |
Operating Temperature |
-10℃-40℃ |
Humidity |
5-90%RH |
Elevation |
<4500m |
GD-4132 Cable Fault Locator
● Acoustic and magnetic signal are received at the same time. Strong anti-interference ability.
● Waveform display.
● Acoustic magnetic waveform display.
● Locating the fault point and route tracing.
● With earphone to hear noise.
● 320*240 LCD screen display, friendly interface.
● Built-in Li battery, with fast charger.
● It will power off automatically if not operating after 15mins or low battery.
● Small size, easy to carry.
Specifications
● Acoustic signal bandwidth: center frequency 400Hz, bandwidth 200Hz
● Signal gain: 80db.
● Locating accuracy: 0.1m
● Power supply: built-in Li battery, nominal voltage 7.4V, 3000mAh, continuous working 9hours.
● Charger: Input AC220V±10%, 50Hz, nominal output 8.4V, DC1A
● Charging time: <4 hours
● Dimension: 270*150*210mm.
● Weight: 1.5kg.
● Use condition: temperature -10–40℃, humidity 5-90%RH, altitude <4500m.
Product detail pictures:
Related Product Guide:
To become the stage of realizing dreams of our employees! To build a happier, much more united and far more professional team! To reach a mutual profit of our clients, suppliers, the society and ourselves for OEM Best Wire Tracer Exporters – GD-4138H Cable Fault Locating System – HV Hipot , The product will supply to all over the world, such as: Istanbul, Portugal, Ottawa, Many years of work experience, we have now realized the importance of providing good quality products and solutions and the best before-sales and after-sales services. Most problems between suppliers and clients are due to poor communication. Culturally, suppliers can be reluctant to question things they do not understand. We break down those barriers to ensure you get what you want to the level you expect, when you want it. faster delivery time and the product you want is our Criterion .
By Arlene from USA - 2018.10.31 10:02
This manufacturers not only respected our choice and requirements, but also gave us a lot of good suggestions, ultimately, we successfully completed the procurement tasks.
By Henry from Zambia - 2017.05.02 11:33