    GDHX-9000 Phase Detector hits:

    Product description

    GDHX-9000 is used for phase detection of power supply on both sides of closed-loop point circuit breaker, in order to avoid short-circuit in power system. It is composed of three parts, a transmitter, a receiver and an adjustable insulated rod. The receiver will indicate test result of in-phase or out of phase. It allows two engineers to proceed the test.


    Features

    • Power supply: Maintenance-free battery with large capacity and very low consumption (Lasting for one year after a single charge). Suitable for field work.
    • Safe design, in accordance with safety standards for mining equipment.
    • Far measuring distance,up to 200M. Signals can be received through the wall.
    • LCD show data such as phase position, waveform, and frequency synchronously, which guarantees an overall and safe test.
    • Extended insulation rod, portable receiver.
    • Small size and light weight.


    Specifications

    • Detectable voltage range: 0.4-500kV(standard is 6-110kV).
    • lWireless transmission distance:  200M of visibility range(customized for more than 300M).
    • Accuracy: 0.1°
    • Definition: phase angle 30°, In-phase; Phase angle 30°, Out of phase.
    • Working frequency: 45-60Hz.
    • Net weight: 5kg.

    Insulation index:

    • High withstand voltage nylon material for 2pcs transmitters.Insulation level is 80kV/cm.
    • Moisture-proof extended insulation rod.The specifications as as below tables.

    Table 1 Electrical & Mechanical specifications of insulation rod

    Items

    Unit

    Index

    Matin type heat resistance(lengthways)

    >200

    Shock resistance(lengthways)

    MPa/cm

    >147

    Bending degree(lengthways)

    MPa

    >343

    surface resistivity(after water-immersed)

    Ω

    >10x1011

    volume resistivity (normality)

    Ω/cm

    >10x1031

    Table 2 Withstand voltage test parameters for insulation rod

    Voltage (kV)

    Length(m)

    Withstand voltage (kV)

    Time

    (min)

    Result

    Standard value

    Test value

    6-10

    3.2

    44

    5

    Qualified

    35

    3.2

    80

    5

    Qualified

    66-110

    3.2

    254

    5

    Qualified

    220kV

    5.2

    40kV/0.3msection

    5

    Qualifie

    Table 3 specifications of phase detector

    No.

    Test items

    Unit

    Test parameters

    Remark

    3kV

    6kV

    10kV

    35kV

    110kV

    220kV

    500kV

    01

    Starting voltage

    kV

    <0.4

    <0.4

    <0.4

    <0.4

    <0.4

    <0.4

    <0.4

    Qualified

    02

    Transmission distance(range of visibility)

    m

    > 200M

    Qualified

    04

    Leak current

    μA

    <30

    <30

    <30

    <30

    <30

    <30

    <30

    Qualified

    05

    Sound level

    dB

    >75

    >75

    >>75

    >75

    >75

    >75

    >75

    Qualified

    06

    DC voltage

    kV

    3

    6

    10

    35

    110

    220

    500

    Qualified

    07

    Withstand voltage test

    40kV/0.3m(section test)

    Qualified

    08

    Anti-arc test

    kV

    3.6

    7.2

    12

    42

    130

    260

    600

    Qualified

    09

    Anti-short circuit test

    kV

    3.6

    7.2

    12

    42

    88

    176

    400

    Qualified

    11

    Temperature test

    -30~+45

    Qualified

    12

    Humidity test

    %

    95%

    95%

    95%

    95%

    95%

    95%

    95%

    Qualified

    13

    Free fall(3M)

    times

    10

    10

    10

    10

    10

    10

    10

    Qualified

    14

    Impulse test

    times

    1000

    1000

    1000

    1000

    1000

    1000

    1000

    Qualified

    15

    In-phase interference

    kV

    <1.2

    <2.4

    <4

    <14

    <44

    <88

    <200

    Qualified

    16

    Phase reversal interference

    kV

    >1.8

    >3.6

    >6

    >21

    >66

    >132

    >300

    Qualified

    17

    Work environment


    Indoor or outdoor

    Qualified

    18

    Work voltage

    V

    8.7V

    Lithium battery

    19

    Static current

    μA

    < 10

    Qualified

    20

    Dynamic current

    mA

    < 20

    Qualified

    21

    Dynamic power consumption

    W

    <0.2

    Qualified


               
    CONTACT US
    Address: F/10, Block B7, JinYinTan Modern Enterprise City, Dongxihu District, Wuhan, China
    Email: info@hvhipot.com
    Skype: hvhipot@hotmail.com
    Tel: +86-27-85568138
    Fax: +86-27-65606183
    NAVIGATION
  • Company

    Company

  • Product

  • News

  • Services

  • Contact us

  • русский

  • All Rights Reserved Copyright@HV Hipot Electric Co.,Ltd.