GD-4136H Cable Fault system is important tool to maintain all kinds of cables. It uses various detection way to test cable faults, which is suitable for different levels voltage power cables and communication cables.
The system contains below units:
1. GD-2131H Impulse Generator
2. GD-4132 Cable Fault Locator
3. GD-4133 Multi-pulse Cable Fault Tester
4. GD-4133S Multi-pulse Coupler
5. Other accessories
It’s used to generate HV impulse when using impulse flashover method to detect high impedance fault.
Strong burning ability, max.burning power is 1000W, breakdown point can be burned in short time and the resistance of breakdown point is decreased.
If working together with GD-4133 Cable Fault Tester, there are two locating ways:
a. Low voltage pulse: If only using GD-4133, open circuit and low impedance grounding faults of cable can be located, and the length of cable can be measured or wave speed of cable can be detected.
b. High voltage flashover: The discharging pulse voltage waveform of fault point is sampled by discharging sphere gap, which can locate fault distance.
Generate impulse of fixed frequency. If working together with GD-4132 Cable Fault Locator, there are following functions:
a. Audio frequency: locate high impedance, flash-over faults.
b. To pinpoint cable’s route, identify special cable.
c. To metallic breakdown(dead grounding), using magnetic-field measurement to locate accurately.
It also can be used in DC HV withstand test.
Input power supply: AC 220V,50Hz
Output voltage: DC 0-32kV (adjustable)
Rated power: 2kVA
Max.energy: 2048J, 4uF
DC flashover voltage: 32kV
DC flashover current: 63mA
Max.impulse current: 500mA
Discharging method: DC HV, one time, cycle
Cycle discharging time: 3-6 seconds
Environmental temperature:0-40℃
Humidity:<75% RH
Altitude:<1000m
Insulation level: A
Dimension: 430*540*410mm
Weight:about 31kg.
Including main unit, acoustic and magnetic sensor, anti-noise headphone and charger.
It is suitable to test all kinds of power cable with metallic conductor.
Its main function is locating poor insulation point, detecting circuit and depth of power cable.
1. Locating function
a. Acoustic signal transmission band: center frequency 400Hz, bandwidth 200Hz
b. Signal gain: 80dB
c. Locating accuracy: 0.1m
2. Power Supply
a. Built-in Li-battery, nominal voltage 7.4V, capacity 3000mAH.
b. Power consumption: 300mA, continuous working time 9hours.
c. Charger: input AC220V±10%, 50Hz. Nominal output 8.4V, DC 1A
d. Charging time: 4hours
3. Dimension: 270mm*150mm*210mm
4. Weight: 1.5kg.
5. Use condition
Temperature -10℃--40℃, humidity 5-90%RH, altitude <4500m
GD-4133 Cable Fault Locator is used to measure distance between cable faults. It’s easy to operate and with friendly interface.
It can be used alone under the low voltage pulse mode. Under the mode of pulse current,it needs to work with GD-2131 high voltage generator. Under the multiple pulse mode, GD-4133S coupler should be worked together. After distance locating, GD-4132 fault locator should be used for fault pinpointing. These products can be combined into
a set of high performance and innovative cable fault testing system.
Locating methods: |
l Low voltage impulse method l Impulse current method l Multiple impulse method if matched with GD-4133S |
Max. Sampling frequency: |
200MHz |
Gain range: |
0-70dB |
Low voltage impulse voltage: |
30V |
Max.resolution: |
0.4m |
Max. Locating range: |
100km |
Dead zone: |
2m |
Battery: |
Nickel-metal hydride rechargeable batteries,endurance time over 5 hours |
Communication interface: |
USB |
Power supply: |
Input AC220V,50Hz,current 2A,charge for 8 hours |
Dim.: |
274×218×81mm |
Weight: |
3.5kgs |
Operating Temperature: |
-10℃-40℃ |
Humidity: |
5-90%RH |
Elevation: |
<4500m |
It is working together with GD-4133 Cable Fault Detector, used for detecting high impedance leak fault, flashover fault, low impedance earth and open circuit fault of power cables. GD-4133S supplied pulse coupling signal for GD-4133 and isolate it from high voltage equipment.
Using the most advanced technology of multiple pulse and pulse balance. The reflected waveform is more easy to identify.
With safety HV protection, the measuring circuit and high voltage impulse power is electrically isolated.
Easy wiring, safe and reliable.
Pulse voltage: 300V(P-P)
Allowable input impulse voltage: <35kV
Allowable input impulse energy: <2000J
Power input: 220V AC, 50Hz
Dimension: 560*230*220mm
Weight: 7kg.