DC high voltage generator common failure and treatment
1. Abnormal output voltage: it may be caused by a power failure, short circuit or open circuit of the output circuit. The treatment method includes checking the power supply to confirm whether the power supply is normal; Inspect output circuits and repair or replace short or open circuits.
GDZG-300 series DC high voltage generator
2. The output voltage is unstable: it may be caused by power supply fluctuations, load changes or internal components aging. The treatment method includes checking the power supply and solving the fluctuation problem; Make sure the load is stable and check whether internal components need to be replaced or repaired.
3. The temperature is too high: it may be caused by overload, poor ventilation or radiator failure. Treatment methods include reducing the load to prevent overload, providing adequate ventilation and heat dissipation, checking that the radiator is working properly and repairing or replacing it.
4. Arc or discharge phenomenon: it may be caused by electrode wear, aging or pollution of insulating materials, improper electrode spacing and other reasons. Treatment methods include replacing worn electrodes, cleaning or replacing insulation, and adjusting appropriate electrode spacing.
5. Control circuit failure: It may be caused by problems such as damage to control circuit components, connection failure or control signal failure. The treatment method includes checking the control circuit, repairing or replacing the damaged component, and ensuring the normal transmission of the control signal.
It should be noted that before dealing with any generator failure, the power should be cut off and the necessary safety measures should be taken to ensure the safety of the operator. In addition, for those who are not familiar with the maintenance and handling of high-pressure equipment failures, ask professional technicians to repair and handle them.