How to use the ground resistance tester

How to use the ground resistance tester

Grounding resistance is a device that is often used in power industry testing, so how to operate it correctly?

 

接地电阻测量仪

GDCR3000C Grounding Resistance Tester

1. First, check whether the current line, voltage line and ground network line used for the test are open, whether the rust on the ground pile is cleanly removed, and whether the buried depth is appropriate. At the same time, check whether the connection between the test line and the ground pile is connected. On, please reconnect after processing.

2. The length ratio of the current test line to the voltage test line is 1:0.618, and the length of the current test line should be 3-5 times the diagonal of the ground grid.

3. Connect one end of the current test line and the voltage test line to the instrument according to the regular length and then release them in parallel. The other ends are connected to two ground stakes respectively.

4. Check the test line of the universal grounding resistance tester again, and then officially put it into use after confirming that it is correct.

5. After checking that the connection is correct, connect the power to the instrument and power on the instrument.

6. Press the measurement key to start the measurement.

7. After the instrument displays the test, record the test data.

8. After turning off the power of the instrument, remove the connection, and the test process is completed.

General grounding resistance tester operating instructions (for reference only):

1. Turn on the power switch, and the computer will perform a self-check.

2. Move the cursor to each menu item and cycle to indicate. The selected item is displayed in reverse white font.

3. On the item currently displayed by the cursor, press the up and down keys to change the menu, and cycle instructions.

4. After changing the menu to correspond to the test requirements, you can press the select button to select the next item.


Post time: Apr-13-2022